DETERMINE LOCATION FOR OUTDOOR TEMPERATURE SENSOR
The location of the Outdoor
Temperature Sensor
FIGURE 3 – OUTDOOR TEMPERATURE SENSOR LOCATION
must meet the following
requirements (see FIGURE 3):
1. Must be mounted out
of direct sunlight on the
North, East or West side
of the house.
2. Must be at least 3 feet
from all exhaust vents.
OUTDOOR
3. Must be above the
TEMPERATURE
SENSOR LEADS
expected snow line.
A convenient way to route the sensor wire outside is to make used of unused wires running to
the A/C condensing unit (if applicable). Other ways are to use existing holes for Cable TV lines,
telephone lines, AC line, etc.
ELECTRICAL INTERFERENCE CAN CAUSE OUTDOOR TEMPERATURE SENSOR INACCURACY.
• Do not run Outdoor Temperature Sensor alongside wires carrying high voltage
(120VAC or higher).
• Do not run Outdoor Temperature Sensor wire lengths greater than 100 feet.
Run wire from the humidistat to the Outdoor Temperature Sensor. Secure the sensor bracket with
a #8 screw.
6 English
NORTH, EAST
OR WEST SIDE
TEMPERATURE
OF HOME
SENSOR
BRACKET
ABOVE EXPECTED
SNOW LINE
NOTICE

WIRING DIAGRAMS

TERMINAL DESCRIPTIONS

1
OUTDOOR
2
SENSOR
3
6
SENSOR
7
8
9
10
11
12
90-998
13
14
15
16

JUMPER SETTINGS

JP2
DIGITAL OUTPUT
SIGNAL SELECTOR
MODE
JP3
SELECTOR
TEMPERATURE SENSOR
Humidistat Back
Common
24VAC
Window temperature sensor or outside temperature sensor input (AI3)
Not Used
Relay Common
Humidify dry or powered contact (see JUMPER SETTINGS)
Dehumidify dry contact (NOT USED)
Humidify set point analog output (NOT USED)
Alarm status digital input (NOT USED)
External humidity sensor
Outdoor temperature sensor
Humidify analog output (see STEP 6)
Dehumidify analog output (NOT USED)
Actual humidity output (NOT USED)
DIGITAL OUTPUT SIGNAL SELECTION (JP2)
Jumper (JP2)
TB1
on left: 24VAC
powered contacts
24VAC
when wiring
Terminals 7 and 8.
CONNECTING
MODE SELECTION (JP3)
STRIP TB1
Jumper (JP3) on
RUN: Humidistat
JP3
is in Operation
RUN
Mode. Humidistat
PGM
set point is
adjustable.
Jumper (JP2)
on right: 24VAC
dry contact when
24VAC EXT.
wiring terminals 7
and 8.
Jumper (JP3) on
PGM: Humidistat
is set in Program
JP3
Mode. Refer to
RUN
the set up section
for instructions.
PGM
Humidistat will
not operate in this
mode.