Removal of Electrical Component ASSY

2. Removal of Electrical Component ASSY
Procedure
Step
Pull out the terminal
1
(blue) for compressor
from K1M (1).
2
Pull out the 2 terminals
(red, yellow) from the
compressor capacitor
(C1R).
Remove the electrical
3
component ASSY.
10
Warning
Be sure to for wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
2
4
6
14
A2
K1M
C1R
to compressor
(R terminal) :
red
K1M
to compressor
(C terminal):
blue
1
3
5
13
A1
(R17468)
to compressor
(S terminal) :
yellow
(R17469)
C2R
F1U
C1R
V1R
F1U
K1M
C1R
C2R V1R
(R16406)
Si011186
Points
Compressor lead wire
S(W)
C(U)
R(V)
(R15393)
S(W) : yellow
C(U) : blue
R(V) : red
Removal Procedure