Typical Operating Characteristics - Lennox EL296UHE Series Unit Information

Table of Contents

Advertisement

V-TYPICAL OPERATING CHARACTERISTICS
A-Blower Operation and Adjustment
1 - Blower operation is dependent on thermostat control
system.
2 - |Generally, blower operation is set at thermostat
subbase fan switch. With fan switch in ON position,
blower operates continuously. With fan switch in
AUTO position, blower cycles with demand or runs
continuously while heating or cooling circuit cycles.
3 - Depending on the type of indoor thermostat, blower
and entire unit will be off when the system switch is
in OFF position.
B-Temperature Rise (Figure 54)
Temperature rise for EL296UHE units depends on unit in-
put, blower speed, blower horsepower and static pressure
as marked on the unit rating plate. The blower speed must
be set for unit operation within the range of "TEMP. RISE
°F" listed on the unit rating plate.
°
TEMPERATURE RISE
Supply Duct Temperature ________
Return Duct Temperature
Temperature Rise = ________
FIGURE 54
_
_____
SUPPLY
AIR
Temperatures
RETURN AIR
Page 49
C-External Static Pressure
1 - 1 - Tap locations shown in figure 55.
2 - Punch a 1/4" diameter hole in supply and return
air plenums. Insert manometer hose flush with
inside edge of hole or insulation. Seal around the
hose with permagum. Connect the zero end of the
manometer to the discharge (supply) side of the
system. On ducted systems, connect the other end
of manometer to the return duct as above.
3 - With only the blower motor running and the
evaporator coil dry, observe the manometer
reading. Adjust blower motor speed to deliver the
air desired according to the job requirements. For
heating speed (second stage heat speed) external
static pressure drop must not be more than 0.5"
W.C. For cooling speed (second stage cool speed)
external static pressure drop must not be more than
0.5" W.C.
4 - Seal the hole when the check is complete.
EXTERNAL STATIC PRESSURE
Supply Duct Static ________
Return Duct Static + _____
Total Duct Static = ________ (dry coil)
FIGURE 55
Supply Air
Duct Static
or
Return Air

Advertisement

Table of Contents
loading

Table of Contents