Table 5.1 Marshallable Binary Input Functions - Siemens SIPROTEC 7SD600 System Manual

Numerical line differential protection
Hide thumbs Also See for SIPROTEC 7SD600:
Table of Contents

Advertisement

Numerical line differential protection SIPROTEC 7SD600 V3.0
A
6 1
R O U T
B
B I
Use the " key to go to the first binary input:
A
6 1
R O U T
B
B I 1
Switch to the selection level with the "key:
6 1
B I 1
1
A
> Res. LED
6 1
B I 1
2
A
not a l l.
The "+" key lets you call up all marshallable input
functions on the display once you have entered the
code word. The "-" key also lets you scroll back
wards through the list of alternatives. The required
function is confirmed with the enter key E. Additional
functions under further index numbers (1 to 10) can
then be selected for binary input 1 using the B key.
Table 5.1
Marshallable binary input functions
Fno.
Short text
(display on LCD)
2
not all.
5
>Res. LED
1157
>CBcl
3003
>DIFblk
3008
>Res.LO
3303
>REM blk
3306
>Rem.Tr.
3333
>Rem.Tr.bl
3363
>PWM bl
Siemens AG January 1999
Preparation instructions
[6100]
Beginning of the block "Marshalling of binary inputs"
"
[6101]
Assignment of binary inputs 1
"
[6102]
Reset memorized LED, Fno. 5;
B
activated with voltage: if input is activated, the LEDs
are reset
[6103]
No further functions are activated by input 1.
Y
B
Each selection must be confirmed with the E key. If
the slot of a physical module is not assigned, the
"not all." function (not allocated) is selected.
You can exit the selection level of binary input 1 with
the A key. The B key takes you to the next binary
input.
Logical function
Input has not been allocated to a function
Reset LEDs
Circuit-breaker auxiliary contact: all poles activated
Blocking of DIF protective function
Reset Lockout function
Blocking of remote tripping
Inter trip of remote station
Blocking of trip by remote station
Blocking of pilot wire monitoring
System manual
Order no. E50417-G1176-C069-A1
5