Replacing the infrared cover

• Engage the infrared cover in the grooves in the chassis, taking care not to lose the
staple. (1)
• Slide the cover upwards until it is stopped by the top plate. (2)
• Place it flat along the chassis, then slide it downwards and screw in the cover fixing
screw. (3)
9.

Final tests

After installation, make sure everything is working with an overall system test.
For SB250 and SB2100 detectors:
• Interupting the beam (intruder alarm).
• Prolonged interuption of the beam for more than 1 minute (interuption alarm).
For SB450, SB4100 and SB4200 detectors:
• Interupting the beam of just one of the two cells: alarm not triggered.
• Interupting the beam of both cells: intruder alarm.
• Prolonged interuption of both beams for more than 1 minute (interuption alarm).

10. Regular maintenance

To keep good ongoing performance levels, minimal maintenance is required:
• Clean the infrared covers of each module at least once a year (or more often,
depending on exposure to soiling).
• Repeat the final tests (once a year).