AC Error - Wire Check
1. Check the connection of the wire.
Figure 42
Control Board
Figure 43
DHW Sensor
AC Error - DHW Sensor Check
1. Measure the resistance of the DHW sensor. If the resistance is not normal,
replace the DHW sensor.
Disconnection: OL
Normal:      86 °F: 40 kΩ
140 °F: 12.4 kΩ
185 °F: 3.9 kΩ
Figure 44
Singular Combi Boiler - BTC 439002301 A (12.2021)
AC Error - Disconnection Check
1. Check if the sensor is disconnected.
Disconnection: OL
Normal:      86 °F: 40 kΩ
140 °F: 12.4 kΩ
185 °F: 3.9 kΩ
Figure 45
AC Error - Short Circuit Check
1. Check if the DHW sensor has short-circuited.
Short circuit: 0 Ω
Normal:      86 °F: 40 kΩ
140 °F: 12.4 kΩ
185 °F: 3.9 kΩ
Figure 46
AC Error - Control Board Check
1. If the wire connection and the resistance of the DHW Thermistor are normal,
replace the control board.