Model Ycul0060C - York MILLENNIUM YCUL0016SC Assembly, Installation, Operation & Maintenance

Air-cooled condensing units hermetic scroll
Table of Contents

Advertisement

Installation
76
67
POWER ENTRY
(2) 64, 51, 38 CONDUIT K.O.'S
(5) 13 CONDUIT K.O.'S
All dimensions are in mm
unless specified otherwise.
SYS. 1 SUCT.
STOP VALVE
WITH 54 O.D.
SUCT. CONN.
SYS. 1 LIQ.
STOP VALVE
W/ 22 O.D.
LIQ. CONN.
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated
performance, reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated
below, resulting in unpredictable airflow patterns and possible diminished performance. YORK's unit controls will optimize
operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance
degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended mini-
mum clearances: Side to wall – 2m; rear to wall – 2m; control panel to end wall – 1.2m; top – no obstructions allowed;
distance between adjacent units – 3m. No more than one adjacent wall may be higher than the unit.
80
DIMENSIONS - YCUL0060SC (METRIC)
76
38
127
127
668
340
737
38
76
CONTROL ENTRY
(8) 13 CONDUIT K.O.'S
VIEW B-B
725
2045
25 TYP.
98
102
51
SYS. 2 SUCT.
STOP VALVE
WITH 54 O.D.
SUCT. CONN.
SYS. 2 LIQ.
STOP VALVE
SYS. 2
22 O.D.
LIQ. CONN.
733
664
6
YORK INTERNATIONAL
LD05747
LD05748