Table 17: Technical Specifications of the Delta PCS100
Item
Grid-tied Operation
Rated Grid Voltage
Grid Voltage Range
Rated Grid Frequency
Frequency Range
Rated AC Power
Rated AC Current
Max. Continuous AC Current
Current THD
Power Factor
Charging-discharging transfer time
Power response time
Battery Input Performance
DC Voltage Range
Rated DC Voltage
Rated Discharge Power
Rated Charge Power
Max. Discharge DC Current
Max. Charge DC Current
Standalone Mode Performance
Rated Output Voltage
Rated Output Power
Rated Output Current
Rated Output Frequency
Power Factor
Output Voltage Accuracy
Voltage Symmetry
Output Voltage THD
Output Voltage Regulation
Installation Manual
400 Vac, 3 phase
312 to 459 Vac
50 Hz (60 Hz optional)
45 to 55 Hz, adjustable
100 kVA
144.3 A
160.4 Arms
< 3% at rated power
-1 to 1, continuously adjustable
< 100 ms
< 40 ms
600 to 1,000 Vdc
900 Vdc
103 kW
97 kW
171.7A
161.7A
400V, 3P3W
(3P4W, extra transformer needed )
100kVA/ 100kW with linear load
100kVA with RCD load (CF≤ 2)
144.3 A
50 Hz ± 1%
0.8 to 1
1%
± 1%, @ 100% linear balanced load
< 3% @ 12.5 ~ 100% liner load
< 5% @ 12.5 ~ 100% RCD load (Crest factor ≤ 2.0)
< 10%, at dynamic; Recovering within tolerance in 100 ms
60