LG PQDSB Owners & Installation Manual page 14

Dry contact for communication
Table of Contents

Advertisement

Setting and using method
5) Compressor stop mode
CONTROL_
MODE S/W
B
➲ Compressor stop mode: The compressor is stopped during cool/heat operation.
6) Operating mode selection mode
CONTROL_
MODE S/W
C
D
➲ Power save mode: Adjust the set temperature to +3°C for cooling and -3°C for heating.
14 Dry contact for communication
Input A
Input B
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Input A
Input B
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Operating mode
Indoor unit operating (Compressor in stop mode), locked
Indoor unit prior operating condition maintained
(Compressor not in stop mode), unlocked
Indoor unit stopped, locked
Indoor unit stopped, locked
Operating mode
Indoor unit stopped, unlocked
Indoor unit in cool/high operation, unlocked
Indoor unit in heat/high operation, unlocked
Indoor unit in fan/high operation, unlocked
Indoor unit stopped, locked
Indoor unit in cool/high operation, locked
Indoor unit in heat/high operation, locked
Indoor unit in fan/high operation, locked