J. LIGHT FUEL OIL PIPING SYSTEM
Adjustment of this equipment and its components by
unqualified personnel can result in fire, explosion, severe
personal injury, or even death.
Eclipse recommends the use of oil manifolds that meet
NFPA guidelines. NFPA requires two safety shutoff
valves piped in series in the burner's main oil line. A
low/high oil pressure switch must be interlocked with the
burner's safety shutoff valves. Eclipse oil manifolds have
been designed to ensure compliance to NFPA
requirements.
1. Eclipse recommends using a flexible connection to connect the oil line to the oil manifold
on the burner. A flexible connection will reduce vibration stress on the oil manifold.
Refer to Table 7 for recommended flex connection.
2. For recommended piping sizes see Table 8. Before attaching fuel lines, purge the
piping to remove scale and dirt that could clog and damage oil equipment. Follow Figure 5
for the suggested piping layout.
Discharge Piping, Light Oil
Up to 100 SSU
(Up to 2.1 x 10
MegaStar
Up to 25'
Model No.
(Up to
7.6m)
25 - 50
1"
(DN25)
75
1"
(DN25)
100
1"
(DN25)
125
1"
(DN25)
150
1"
(DN25)
Table 8. Minimum Pipe Size For Hauck Oil Supply Pumping Units
3. Adjust the bypass relief valve until required oil pressure is achieved. See Table 9 for
approximate settings. Final oil pressure will have to be adjusted to attain desired burner
output and stack exhaust gas analysis.
MegaStar™ Model No.
Flex Oil Hose Part No.
Size
Table 7. Recommended Flexible Oil Hose Size
m
/sec)
-5
2
25'– 49'
50' – 100'
Up to 25'
(7.6-
(15.2-
(Up to
14.9m)
30.5m)
7.6m)
1"
1 ¼"
(DN25)
(DN32)
(DN25)
1"
1 ¼"
(DN25)
(DN32)
(DN25)
1"
1 ¼"
(DN25)
(DN32)
(DN32)
1 ¼"
1 ½"
(DN32)
(DN40)
(DN32)
1 ¼"
1 ½"
(DN32)
(DN40)
(DN32)
WARNING
NOTE
25 - 50
HK11078
HK20518
1/2" (DN 15)
1" (DN 25)
Return Piping, Light Oil
Up to 100 SSU
(Up to 2.1 x 10
m
/sec)
-5
2
25' – 49'
50' – 100'
(7.6-
(15.2-
14.9m)
30.5m)
1"
1 ¼"
1 ¼"
(DN32)
(DN32)
1"
1 ¼"
1 ¼"
(DN32)
(DN32)
1 ¼"
1 ¼"
1 ¼"
(DN32)
(DN32)
1 ¼"
1 ¼"
1 ½"
(DN32)
(DN40)
1 ¼"
1 ¼"
1 ½"
(DN32)
(DN40)
Page 14
MS-9
75-150
Return Piping
Heavy Oil
Up to 25'
25'– 49'
(Up to
(7.6-
7.6m)
14.9m)
1 ¼"
1 ½"
(DN32)
(DN40)
1 ¼"
1 ½"
(DN32)
(DN40)
1 ¼"
1 ½"
(DN32)
(DN40)
1 ½"
2"
(DN40)
(DN50)
1 ½"
2"
(DN40)
(DN50)
50' – 100'
(15.2-
30.5m)
2"
(DN50)
2"
(DN50)
2"
(DN50)
2"
(DN50)
2"
(DN50)

Advertisement