Commissioning, inspection, maintenance
Checking the CO
3. Check control cables:
Connection and kink-free routing
Application and seating of retaining clips
4. If the CO
content needs adjusting:
2
Turn adjusting screw
tinue turning until CO
specified range.
Turn towards "
"
CO
content falls.
2
Turn towards "+"
CO
content rises.
2
CO
test at the lower heating output
2
B
A
Fig. 10
1. Press
until the service display has counted down
to "0" (lower heating output).
2. Check the CO
content at the flue pipe.
2
For permissible CO
content, see above table
2
(page 17).
Note
At the lower heating output, the CO
always be lower than at the upper heating output.
18
content
(cont.)
2
in small increments. Con-
A
content falls within the
2
content must
2
5. Enter actual value into the report in the appendix.
3. If the CO
content needs adjusting:
2
Turn adjusting screw
B
Continue turning until CO
specified range.
Turn towards "
"
CO
content falls.
2
Turn towards "+"
CO
content rises.
2
4. Enter actual value into the report in the appendix.
in very small increments.
content falls within the
2