Honeywell BCU 460 Technical Information page 66

Burner control units
Hide thumbs Also See for BCU 460:
Table of Contents

Advertisement

Parameters
Name
Flameless operation
Operating time in Manual mode
Combustion mode
Air actuator (bus)
Auxiliary gas function
Burner application
Fieldbus communication
K-SafetyLink
Safety interlocks (bus)
Purge (bus)
BCU 460, BCU 465 · Edition 11.19
Parameter
Value range
Description
0
Upon next burner start
A064
1
Immediate burner start
2
Immediate switchover
0
Unlimited
A067
1
5 minutes
0
Flame mode
A074
1
Flameless/menox®
2
High temperature operation without ignition
0
Off
1
MIN. to MAX. capacity; standby in position for MIN.
capacity
2
MIN. to MAX. capacity; standby in CLOSED position
A075
3
IGNITION to MAX. capacity; standby in CLOSED position
4
MIN. to MAX. capacity; standby in position for MIN.
capacity; burner quick start
5
IGNITION to MAX. capacity; standby in CLOSED position;
burner quick start
0
Off
1
Flame mode
A077
2
Flameless operation
3
Operation
0
Burner 1
1
Burner 1 with pilot gas
A078
4
Two-stage burner 1
13
Flameless 1/0 with 2 gas paths
0
Off
A080
1
With address check
2
No address check
0
Off
A081
1
On
1
Via fail-safe bus (K-SafetyLink)
A085
2
Via terminal
5
Via fail-safe bus (K-SafetyLink) and terminal
0
Off
1
Via fail-safe bus (K-SafetyLink)
A087
2
Via terminal
3
Via non-fail-safe bus
4
Via fail-safe bus (K-SafetyLink) or terminal
Factory default
settings
1
1
1
0
0
0
0
0
2
2
66