Viessmann Vitodens 242-F Installation And Service Instructions Manual page 86

Gas/solar condensing storage combi boiler
Table of Contents

Advertisement

Code 2
"Heating circuit ..."
Parameter address
With heating circuit pump logic function:
b5:...
Heating circuit pump "OFF"
3
RT
4
RT
5
RT
6
RT
7
RT
8
RT
Coding in the delivered condition
C5:20
Electronic minimum flow tempera-
ture limit 20 °C (only for operation
with standard room temperature)
C6:74
Electronic maximum flow tempera-
ture limit 74 °C (only for weather-
compensated control units)
d3:14
Heating curve slope = 1.4
d4:0
Heating curve level = 0
d5:0
With external heating program
changeover (observe setting for
coding addresses "3A", "3b" and
"3C" in the "General" group).
Heating program switches to "Con-
stant central heating with reduced
room temperature" or "Standby
mode" (subject to the value selec-
ted for the set reduced room tem-
perature).
d6:0
Heating circuit pump stays in con-
trol mode at signal "External block-
ing"
d7:0
Heating circuit pump stays in con-
trol mode at signal "External de-
mand"
d8:0
With EA1 extension:
No operating program changeover.
E1:1
Do not adjust
E2:50
With remote control:
86
(cont.)
RT
+ 3 K
>
actual
set
RT
+ 2 K
>
actual
set
RT
+ 1 K
>
actual
set
RT
>
actual
set
RT
1 K
>
actual
set
RT
2 K
>
actual
set
Heating circuit pump "ON"
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
Possible change
C5:1
Minimum limit adjustable from 1 to
to
127 °C (limited by boiler-specific pa-
C5:127
rameters)
C6:10
Maximum limit adjustable from 10 to
to
127 °C (limited by boiler-specific pa-
C6:127
rameters)
d3:2
Heating curve slope adjustable from
to
0.2 to 3.5 (see page 64)
d3:35
d4:–13
Heating curve level adjustable from
to
13 to 40 (see page 64)
d4:40
d5:1
Heating program switches to "Con-
stant operation with standard room
temperature".
d6:1
Heating circuit pump stops at "Exter-
nal blocking" signal (subject to cod-
ing addresses "3A", "3b" and "3C")
d6:2
Heating circuit pump starts at "Exter-
nal blocking" signal (subject to cod-
ing addresses "3A", "3b" and "3C")
d7:1
Heating circuit pump stops at "Exter-
nal demand" signal (subject to cod-
ing addresses "3A", "3b" and "3C")
d7:2
Heating circuit pump starts at "Exter-
nal demand" signal (subject to cod-
ing addresses "3A", "3b" and "3C")
d8:1
Operating program changeover via
input DE1.
d8:2
Operating program changeover via
input DE2.
d8:3
Operating program changeover via
input DE3.
E2:0
Display correction
to
to
+ 2 K
+ 1 K
1 K
2 K
3 K
5 K