Siemens SINAMICS G120 Compact Operating Instructions page 2

Hide thumbs Also See for SINAMICS G120:

Advertisement

Feature
Specification
Line voltage
3 AC 380 V ... 480 V ± 10 % up to 2000 m installation altitude. 1 AC / 3 AC 200 V ... 240 V ± 10 % up to 2000 m installation altitude.
Output voltage
3 AC 0 V ... input voltage * 0.95
Input frequency
50 Hz ... 60 Hz, ± 3 Hz
Output frequency
0 Hz ... 550 Hz, depending on the control mode
Power factor
0.7 without line reactor; 0.85 with line reactor
< LO base load input current
Irrush current
Pulse frequency (factory setting)
4 kHz. Can be increased in 2 kHz steps up to 16 kHz. Increasing the pulse frequencies leads to an output current reduction.
Interference emission: The devices are suitable for second environment category C2 in accordance with IEC 61800-3 if the following
Electromagnetic compatibility
conditions are fulfilled: The motor cable is a shielded cable with low capacitance and is not longer than 50 m. The pulse frequency does
not exceed 4 kHz, the current does not exceed the LO input value. For details, refer to the Hardware Installation Manual.
Interference immunity: The devices are suitable for second environment category C3
Braking methods
DC braking, Compound braking, Dynamic braking with integrated chopper plus external braking resistor
Bulit-in units (open type equipment): IP20
Environmental rating
Push-through units: IP54/UL Type 12 when mounted on a flat surface of an enclosure
This equipment is capable of providing internal motor overload protection according to UL61800-5-1. The protection level is 115%, 230%
Motor overload protection
and 400% full load current of the equipment. This is adjusted via parameter P640 and assumes the equipment has had basic motor
commissioning for the motor used as described in the documentation.
0 °C ... 40 °C (32 °F ... 104 °F) without current derating / up to 60 °C (140 °F) with current derating
LO operating temperature
1)
0 °C ... 50 °C (32 °F ... 122 °F) without current derating / up to 60 °C (140 °F) with current derating
HO operating temperature
1)
Storage temperature
- 40 °C ... + 70 °C (- 40 °F ... + 158 °F)
Installation altitude above sea level
Up to 1000 m (3300 ft) without derating/ Up to 4000 m (13000 ft) with derating
Humidity
<
95 % RH - non-condensing
Environmental conditions
Suitable for environmental class 3C2 according to IEC 60721-3-3 against damaging chemical substances
For open type equipment according to pollution degree level 2. Protection against conductive pollutions required e.g. using an IP54
Pollution
cabinet.
For enclosed type/push-through equipment according to pollution degree level 3.
Shock
Long-term storage in the transport packaging according to Class 1M2 of IEC 60721-3-1: Transport in the transport packaging according
to Class 2M3 of IEC 60721-3-2. See Hardware Installation Manual for detailed specifications.
Vibration
Long-term storage in the transport packaging according to Class 1M2 of IEC 60721-3-1: Transport in the transport packaging according
to Class 2M3 of IEC 60721-3-2. See Hardware Installation Manual for detailed specifications.
Line impedance
200 V units: Uk 2 %, for lower values, a line reactor must be used.
400 V units: Uk 1 %, for lower values, a line reactor must be used.
Short Circuit Current Rating
Suitable for use on a circuit capable of delivering not more than 100 kA rms symetrical amperes; 240/480 V AC maximum when protected
by Class J fuses.
(SCCR)
Further suitable protective devices including the associated SCCR can be found in:
https://support.industry.siemens.com/cs/ww/en/view/109782705
according to UL, operation with temperatures > 50 °C (122 °F) is not permitted at all
1)
CAUTION - Cable cross-section for grounding: The earth cable must be at least as big as the power cables.
For United States / Canadian installations (UL/cUL): In order that the system is UL/cUL-compliant, use
UL/cUL-certified J-type fuses. Use 75° C copper wire only.
Additional requirements for Canadian compliance:
400 V supply:
Transient surge suppression must be installed on the line side of this equipment and shall be rated 480 V
(phase to ground), 480 V (phase to phase), suitable for overvoltage category III and shall provide protection
for a VPR maximum of 2 kV, type 1 or type 2 SPD application.
200 V supply:
Transient surge suppression must be installed on the line side of this equipment and shall be rated 240 V
(phase to ground), 240 V (phase to phase), suitable for Overvoltage Category III and shall provide protection
for a VPR maximum of 2 kV, type 1 or type 2 SPD application.
Cable lengths, using
EMI level (Emission)
50 m
Screened cables, filtered units (class A)
Second Environment, C2
50 m
Screened cables, unfiltered units
EMI Standard not fulfilled
Unscreend cables, filtered or unfiltered units
100 m
EMI Standard not fulfilled
Overloads
Permissible overload for operation
Permissible overload for operation
according to "Low Overload" (LO)
according to "High Overload" (HO)
%
%
150 % for 3 s
200 % for 3 s
110 % for 57 s
200
150
100 % for 240 s
100
100
LO base load: 100 % LO power
HO base load: 100 % HO power
100 % LO current
t[s]
240
300
0
0
60
120
180
Compact Operating Instructions
Fitting CU to PM
Insert CU
150 % for 57 s
Data regarding the power loss in accordance with Ecodesign Regulation
100 % for 240 s
(EU) 2019/1781 and IEC 61800-9-2
You can find data regading power loss of our products on the Internet:
100 % HO current
t[s]
https://support.industry.siemens.com/cs/ww/en/view/94059311
60
120
180
240
300
Low values
Power
Output
current
kW
hp
A
PM240-2, Built-in units, 3 AC 380 V ... 480 V
0.55
0.75
1.7
0.75
1.00
2.2
1.10
1.50
3.1
1.50
2.00
4.1
2.20
3.00
5.9
3.00
4.00
7.7
4.00
5.00
10.2
5.50
7.50
13.2
7.50
10.00
18.0
11.00
15,00
26.0
15.00
20.00
32.0
PM240-2, Push-through units, 3 AC 380 V ... 480 V
3.00
4.00
7.7
7.50
10.00
18.0
15.00
20.00
32.0
PM240-2, Built-in units, 1 AC/3 AC 200 V ... 240 V
0.55
0.75
3.2
0.75
1.00
4.2
1.10
1.50
6
1.50
2.00
7.4
2.20
3.00
10.4
3.00
4.00
13.6
4.00
5.00
17.5
PM240-2, Built-in units, 3 AC 200 V ... 240 V
5.50
7.50
22.0
7.50
10.00
28.0
PM240-2, Push-through units, 1 AC/3 AC 200 V ... 240 V
0.75
1.00
4.2
2.20
3.00
10.4
4.00
5.00
17.5
PM240-2, Push-through units, 3 AC 200 V ... 240 V
5.50
7.50
22.0
7.50
10.00
28.0
Screening methods
Line
cable
Wire
straps
Remove CU
Shielding brackets
Motor cable
Braking resistor cable
Power Module PM240-2, FSA, FSB, FSC
High values
Rated
Frame
Order No. *)
Power
(LO)
Size
Output
input
current
current
kW
hp
A
A
0.37
0.50
1.3
2.3
F SA
6SL3210-1PE11-8_L1
6SL3210-1PE12-3_L1
0.55
0.75
1.7
2.9
F SA
6SL3210-1PE13-2_L1
0.75
1.00
2.2
4.1
F SA
6SL3210-1PE14-3_L1
1.10
1.50
3.1
5.5
F SA
6SL3210-1PE16-1_L1
1.50
2.00
4.1
7.7
F SA
6SL3210-1PE18-0_L1
2.20
3.00
5.9
10.1
F SA
6SL3210-1PE21-1_L0
3.00
4.00
7.7
13.3
F SB
6SL3210-1PE21-4_L0
4.00
5.00
10.2
17.2
F SB
6SL3210-1PE21-8_L0
5.50
7.50
13.2
22.2
F SB
6SL3210-1PE22-7_L0
7.50
10.00
18.0
32.6
F SC
6SL3210-1PE23-3_L0
11.00
15.00
26.0
39.9
F SC
2.20
3.00
5.9
10.1
F SA
6SL3211-1PE18-0_L1
6SL3211-1PE21-8_L0
5.50
7.50
13.2
22.2
F SB
6SL3211-1PE23-3_L0
11.00
15.00
26.0
39.9
F SC
6SL3210-1PE13-0_L0
0.37
0.50
2.3
7.5
F SA
0.55
0.75
3.2
9.6
F SA
6SL3210-1PE13-8_L0
6SL3210-1PE15-5_L0
0.75
1.00
4.2
13.5
F SB
6SL3210-1PE17-4_L0
1.10
1.50
6
18.1
F SB
6SL3210-1PE21-0_L0
1.50
2.00
7.4
24.0
F SB
6SL3210-1PE21-4_L0
2.20
3.00
10.4
35.9
F SC
3.00
4.00
13.6
43.0
F SC
6SL3210-1PE21-8_L0
4.00
5.00
17.5
28.6
F SC
6SL3210-1PC22-2_L0
6SL3210-1PC22-8_L0
5.50
7.50
22.0
36.4
F SC
6SL3211-1PB13-8_L0
0.55
0.75
3.2
9.6
F SA
1.50
2.00
7.4
24.0
F SB
6SL3211-1PB21-0_L0
3.00
4.00
13.6
43.0
F SC
6SL3211-1PB21-8_L0
6SL3211-1PC22-2_L0
4.00
5.00
17.5
28.6
F SC
6SL3211-1PC22-8_L0
5.50
7.50
22.0
36.4
F SC
Mains, Motor and Brake terminals
The Power Modules are fitted with detachable terminals. It can
be removed from the Power Module by pressing the release
catch. The connectors are not interchangeable.
Tightening torques:
FSA: 0.5 Nm ( 4.5 lbf.in)
Control cable
FSB: 0.6 Nm ( 5.5 lbf.in)
FSC: 1.3 Nm (12 lbf.in)
Cable cross sections
FSA: 1.5 ... 2.5 mm
2
2
FSB: 1.5 ... 6 mm
2
FSC: 6 ... 16 mm
Siemens AG,
Digital Industries
Motion Control
Postfach 3180
91050 ERLANGEN
Germany
SINAMICS G120
Line fuses
Siemens
UL, J-type
3NA3804
(4 A)
10 A
3NA3804
(4 A)
10 A
3NA3801
(6 A)
15 A
3NA3803
(10 A)
15 A
3NA3803
(10 A)
15 A
3NA3805
(16 A)
15 A
3NE1814-0
(20 A)
35 A
3NE1815-0
(25 A)
35 A
3NE1803-0
(35 A)
35 A
3NE1817-0
(50 A)
50 A
3NE1817-0
(50 A)
50 A
3NA3805
(16 A)
15 A
3NE1803-0
(35 A)
35 A
3NE1817-0
(50 A)
50 A
3NA3803
(10 A)
15 A
3NA3805
(16 A)
15 A
3NE1814-0
(20 A)
35 A
3NE1815-0
(25 A)
35 A
3NE1803-0
(35 A)
35 A
3NE1817-0
(50 A)
50 A
3NE1818-0
(63 A)
50 A
3NE1802-0
(40A)
50 A
3NE1817-0
(50A)
50 A
3NA3805
(16 A)
15 A
3NE1803-0
(35 A)
35 A
3NE1818-0
(63 A)
50 A
3NE1802-0
(40A)
50 A
3NE1817-0
(50A)
50 A
*) _: A = filtered unit, U = unfiltered unit
① Mains connector
② Motor connector
③ DC Link connector
④ Release catch
16 ... 14 AWG
16 ... 10 AWG
10 ... 6 AWG
Edition: 04/2021