General Installation Environments; Industrial Environment Installations - Emerson PACSystems RX3i Manual

Controllers battery & energy pack
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

Battery & Energy Pack Manual
GFK-2741J
Specification
Backup trip voltage
Capacitor Pack life
expectancy
Environmental Specifications
The Energy Pack shall be installed in a location that is not exposed to corrosive gases or
liquids, rain, or direct sunlight, and that meets the environmental specifications listed
below.
Operating Temperature, surrounding air
Storage Temperature
Humidity
Environment
3.2.2

General Installation Environments

In order to maintain the
Agency Certifications listed below, installation must comply with the following
requirements.
WARNING
The Energy Pack must be installed in a Restricted Access Area, as defined by:
Access can only be gained by service persons or by users who have been instructed
about the reasons for the restrictions applied to the location and about any precautions
that shall be taken; and
Access is using a tool or lock and key, or other means of security, and is controlled by
the authority responsible for the location.
The Energy Pack must be installed in a Pollution Degree 2 environment as defined by:
3.2.3

Industrial Environment Installations

For use in industrial environments this product is considered open equipment [having live
electrical parts that may be accessible to users] and must be installed in an ultimate
enclosure that is manufactured to provide safety. At a minimum, the enclosure shall provide
a degree of protection against solid objects up to 12mm (0.5") (e.g. fingers). This equates
to a NEMA/UL Type 1 enclosure or an IP20 rating (IEC60529) providing at least a pollution
degree 2 environment.
Energy Packs
Description
19 Vdc ±4% (18.24V to 19.76V)
5 years
Pollution Degree 2 applies where there is only non-conductive pollution that might
temporarily become conductive due to occasional condensation.
-25˚C to 60˚C
-40C to +85C (-40°F to 185°F)
5% to 95%, non-condensing
Restricted Access Area and Pollution Degree 2
environment as defined below.
Chapter 3
Oct 2019
22