Space Required For Unit Installation And Operation - Mitsubishi Electric City Multi PUHY-P-THMU-A Installation Manual

Air-conditioners for building application
Table of Contents

Advertisement

Available languages

Available languages

6. Space required for unit installation and operation

1 In case of single installation
Secure enough space around the unit as shown in the figure below.
[Fig. 6.0.1]
(1) If the distance is 300 mm [11-13/16 in] or more between the rear side and
the wall
<A> Top view
300*
[11-13/16]
A
450*
[17-23/32]
15*
15*
[19/32]
[19/32]
(2) If the distance is 100 mm [3-15/16 in] or more between the rear side and
the wall
<A> Top view
100*
[3-15/16]
A
450*
[17-23/32]
50*
50*
[1-31/32]
[1-31/32]
2 In case of collective installation and continuous installation
[Fig. 6.0.2]
C
B
B
A
C
30
[1-3/16]
C
B
B
A
C
100
[3-15/16]
B
A
A
A
C
C
450*
450
450
100*
[17-23/32] [17-23/32] [17-23/32] [3-15/16]
B
C
A
A
A
450
450
[17-23/32] [17-23/32]
(3) If the wall height (H) of the front, rear or side exceeds the wall height
restriction
<B> Side view
(Unit: mm [in])
B
When the height of the walls on the front, back or on the sides <H> exceeds
the wall height limit as defined here, add the height that exceeds the height
limit <h> to the figures that are marked with an asterisk (*).
<Wall height limit> Front: Up to the unit height
(Unit: mm [in])
(4) If there are obstacles at the upper part of the unit
<C> When there is little space up to an obstruction
45°
240
[9-15/32]
A Front
C Back
C
B
A
C
1000*
[39-3/8]
A Front
C Wall height (H)
When multiple units are installed adjacent to each other, secure enough space
to allow for air circulation and walkway between groups of units as shown in
the figures.
At least two sides must be left open.
As with the single installation, add the height that exceeds the height limit <h>
to the figures that are marked with an asterisk (*).
A
Back: Up to 500mm [19-11/16 in] from the unit bottom
Side: Up to the unit height
1000
[39-3/8]
D
A
50
[1-31/32]
B Unit height
D Air outlet guide (field-supplied)
B
C
B
A
B
B Must be open
(Unit: mm [in])
(Unit: mm [in])
C
(Unit: mm [in])
5