3. Combination of outdoor unit

Component units of PUHY-HP144 to HP192 are listed below.
Outdoor unit model
PUHY-HP72THMU-A(-BS)
PUHY-HP96THMU-A(-BS)
PUHY-HP144TSHMU-A(-BS)
PUHY-HP192TSHMU-A(-BS)
* PUHY-HP144/192TSHMU-A(-BS) require "Twinning Kit" to connect component unit modules in the field.

4. Specifications

Model
Sound level (60Hz)
External static pressure
Total capacity
Indoor units
Model
Quantity
Standard type
Cooling mode: – 5°CDB ~ 43°CDB [23°FDB ~ 109°FDB] (0°CDB ~ 43°CDB [32°FDB ~ 109°FDB] with outdoor unit at lower position)
Operation
Heating mode: – 25°CWB ~ 15.5°CWB [–13°FWB ~ 60°FWB]
temperature
Outside air
Cooling mode: 21°CDB/15.5°CWB ~ 43°CDB/35°CWB (70°FDB/60°FWB ~ 109°FDB/95°FWB)
intake type
Heating mode: – 10°CDB ~ 20°CDB [14°FDB ~ 68°FDB]
*1: The total indoor capacity of units run simultaneously is 130% or less.
*2: To enable high static pressure, set the DipSW on the main panel as follows.
SW3-9: ON, SW3-10 60Pa compatible: OFF, 30Pa compatible: ON

5. Parts included list

1 Connecting pipe (flare)
<Gas side>
P72
Model
P96

6. Space required for unit installation and operation

1 In case of single installation
Secure enough space around the unit as shown in the figure below.
[Fig. 6.0.1]
(1) If the distance is 300 mm [11-13/16 in] or more between the rear side and
the wall
<A> Top view
300*
[11-13/16]
A
450*
[17-23/32]
15*
15*
[19/32]
[19/32]
(2) If the distance is 100 mm [3-15/16 in] or more between the rear side and
the wall
<A> Top view
100*
[3-15/16]
A
450*
[17-23/32]
50*
50*
[1-31/32]
[1-31/32]
4
Component unit models
-
-
PUHY-HP72THMU-A(-BS)
PUHY-HP96THMU-A(-BS)
PUHY-HP72THMU-A
PUHY-HP96THMU-A
56dB <A>
1 ~ 13
2 Connecting pipe (flange)
<Gas side>
1 pc.
1 pc.
(Unit: mm [in])
(Unit: mm [in])
-
-
PUHY-HP72THMU-A(-BS)
PUHY-HP96THMU-A(-BS)
PUHY-HP144TSHMU-A
59dB <A>
57dB <A>
0 Pa*
2
50 ~ 130%*
1
06 ~ 96
1 ~ 16
3 Connecting pipe (flare)
<Liquid side>
1 pc.
1 pc.
(3) If the wall height (H) of the front, rear or side exceeds the wall height
restriction
<B> Side view
B
A
When the height of the walls on the front, back or on the sides <H> exceeds
the wall height limit as defined here, add the height that exceeds the height
limit <h> to the figures that are marked with an asterisk (*).
<Wall height limit> Front: Up to the unit height
(4) If there are obstacles at the upper part of the unit
<C> When there is little space up to an obstruction
45°
240
[9-15/32]
A Front
C Back
PUHY-HP192TSHMU-A
60dB <A>
1 ~ 22
1 ~ 24
4 Adapter
<Check joint>
(Inside ø23, Outside ø30)
2 pcs.
2 pcs.
Back: Up to 500mm [19-11/16 in] from the unit bottom
Side: Up to the unit height
1000
[39-3/8]
D
A
50
[1-31/32]
B Unit height
D Air outlet guide (field-supplied)
5 Packing
1 pc.
(Unit: mm [in])