Group Control Setting - LG ARNU18GTLA2 Installation Manual

Ceiling cassette - 2way
Hide thumbs Also See for ARNU18GTLA2:
Table of Contents

Advertisement

Group Control Setting

1. Group Control 1
■ Wired remote controller 1 + Standard Indoor Units
Master
Display Error Message
Master
■ Dip Switch in PCB (Cassette and Duct Type indoor units)
➀ Master Setting
- No. 3 Off
1. It is possible to 16 indoor units(Max.) by one wired remote controller.
Set only one indoor unit to Master, set the others to Slave.
2. It is possible to connect with every type of indoor units.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
- The Master indoor unit is possible to recognize Dry Contact and Central Controller only.
- In case of Central controller and Group controller at the same time, it is possible to connect stan-
dard 2series indoor units or later since Feb. 2009.
- In case of Central controller setting, the Central controller can control indoor units after setting only
the address of master indoor unit.
- Slave indoor unit will be operated like master indoor unit.
- Slave indoor unit can not be individually controlled by Central controller.
- Some remote controller can't perform with Dry Contact and Central controller at the same time.
So contact us further information about it.
or
Slave
➁ Slave Setting
- No. 3 On
Indoor Unit DIP Switch
LGAP Network System
Slave
Only connect serial signal and
GND lines between indoor units.
Installation Manual 13
Installation
GND
Signal
Slave
12 V