2. Align the center of the pipings and sufficiently
tighten the flare nut by hand
3. Finally, tighten the flare nut with torque
wrench until the wrench clicks.
I When tightening the flare nut with torque
wrench, ensure the direction for tightening
follows the arrow on the wrench.
CAUTION: Use two wrenches and
tighten with regular torque.
Flaring Work and Connection of Piping
Outdoor unit
B-UNIT
A-UNIT
Liquid side piping
Torque
wrench
Outside diameter
mm
inch
Ø6.35
1/4
Ø9.52
3.8
Ø12.7
1/2
Ø15.88
5/8
Ø19.05
3/4
Liquid side piping
Gas side piping
Torque
kgf . cm
180~250
340~420
550~560
630~820
990~1 210
Installation Manual 33