Carrier 58SU0A Series Installation, Start-Up, Operating And Service And Maintenance Instructions page 7

4-way multipoise induced-combustion, 80% afue gas furnace input capacities: 40,000 thru 100,000 btuh
Table of Contents

Advertisement

WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Do not install the furnace on its back or hang furnace with
control compartment facing downward. Safety control
operation will be adversely affected. Never connect
return- -air ducts to the back of the furnace. (See Fig. 6)
Fig. 6 - - Prohibit Installation on Back
CAUTION
!
FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace damage.
Air for combustion must not be contaminated by halogen
compounds, which include fluoride, chloride, bromide, and
iodide. These elements can corrode heat exchangers and
shorten furnace life. Air contaminants are found in aerosol
sprays, detergents, bleaches, cleaning solvents, salts, air
fresheners, and other household products.
LOCATION RELATIVE TO COOLING EQUIPMENT
The cooling coil must be installed parallel with, or on the
downstream side of the unit to avoid condensation in the heat
exchangers. When installed parallel with the furnace, dampers or
other flow control must prevent chilled air from entering the
furnace. If the dampers are manually operated, they must be
equipped with means to prevent operation of either unit unless
the damper is in the full- -heat or full- -cool position.
AIR FOR COMBUSTION AND
VENTILATION
Provisions for adequate combustion, ventilation, and dilution air
must be provided in accordance with:
S
U.S. installations: Section 9.3 of the current edition of
NFGC NFPA54/ANSI Z223.1, Air for Combustion
and Ventilation, and applicable provisions of the local
building codes.
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury
or death.
The operation of exhaust fans, kitchen ventilation fans,
clothes dryers, attic exhaust fans or fireplaces could create a
NEGATIVE PRESSURE CONDITION at the furnace.
Make- -up air MUST be provided for the ventilation devices,
in addition to that required by the furnace. Refer to Carbon
Monoxide Poisoning Hazard warning in venting section of
these instructions to determine if an adequate amount of
make- -up air is available.
The requirements for combustion and ventilation air depend upon
whether or not the furnace is located in a space having a volume
of at least 50 cubic feet per 1,000 Btuh input rating for all gas
appliances installed in the space.
S
Spaces having less than 50 cubic feet per 1,000 Btuh
require the OUTDOOR COMBUSTION AIR
METHOD.
S
Spaces having at least 50 cubic feet per 1,000 Btuh
may use the INDOOR COMBUSTION AIR,
STANDARD or KNOWN AIR INFILTRATION
METHOD.
A02054
Outdoor Combustion Air Method
1. Provide the space with sufficient air for proper
combustion, ventilation, and dilution of flue gases using
permanent horizontal or vertical duct(s) or opening(s)
directly communicating with the outdoors or spaces that
freely communicate with the outdoors.
2. Fig. 7 illustrates how to provide TWO OUTDOOR
OPENINGS, one inlet and one outlet combustion and
ventilation air opening, to the outdoors.
a. One opening MUST commence within 12- -in. (300 mm)
of the ceiling and the second opening MUST commence
within 12- -in. (300 mm) of the floor.
b. Size openings and ducts per Fig. 7 and Table 2.
12 " MAX
(305mm)
1 SQ IN.
PER 2000
BTUH*
DUCT S
TO
OUTDOORS
1 SQ IN.
PER 2000
BTUH*
12 " MAX
(305mm)
CIRCULA TING AIR DUCT S
*Minimum dimensions of 3 in. (76 mm).
NOTE: Use any of the following combinations of openings:
A&B, C&D, D&E, F&G
Fig. 7 - - Air for Combustion, Ventilation, and Dilution from
7
WARNING
1 SQ IN.
PER 4000
DUCTS
BTUH*
TO
O UTDOORS
D
VENT
B
THR OUGH
F
R OOF
1 SQ IN .
1 SQ IN .
E
G
A
C
12 " MAX
(305mm)
DUCT
1 SQ IN.
TO
PER 4000
OUTDOORS
BTUH*
Outdoors
12 "
(305mm)
MAX
PER
4000
BTUH*
PER
4000
BTUH*
12 "
(305mm)
MAX
A03174

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents