Removal Of Indoor Heat Exchanger - Daikin FTKS20KVLT Service Manual

Removal procedure
Table of Contents

Advertisement

Si041049

10.Removal of Indoor Heat Exchanger

Procedure
Step
1. Disconnect the refrigerant
piping.
1
Remove the screws
which fix the indoor
heat exchanger to the
installation plate.
Lift the indoor unit with
2
a wooden base.
Lift up the indoor unit
3
slightly and pull out the
drain hose. (The
illustration is for the
case of left piping.)
4
Disconnect the gas
piping and the liquid
piping.
Removal Procedure
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
Drain hose
Removal of Indoor Heat Exchanger
Points
Preparation
Remove the electrical box
according to the "Removal of
Electrical Box".
Caution
If the refrigerant leaks, repair
the leakage, then collect all
refrigerant from the unit. After
conducting vacuum drying,
recharge the proper amount
(R8103)
of refrigerant.
Caution
From the viewpoint of global
environment protection, be
sure to use a vacuum pump
for air purging.
Caution
In pump-down work, be sure
to stop the compressor
before disconnecting the
(R8104)
refrigerant piping. If the
refrigerant piping is
disconnected with the
compressor operating and
the stop valve open, air may
be sucked in to generate an
over-pressure in refrigeration
cycle, thus resulting in pipe
rupture or accidental injury.
Place a plastic sheet under
the drain pan to prevent from
(R8101)
wetting the floor with the
remaining drain.
If the drain hose is
embedded in the wall,
disconnect the drain hose
beforehand.
Carry out the removal work
with 2 wrenches.
When the pipings are
disconnected, protect both
(R8105)
the openings of pipe and unit
from entering moisture.
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents