Checklist - Wolf KG Installation And Maintenance Instructions Manual

Air-handling unit
Hide thumbs Also See for KG:
Table of Contents

Advertisement

Recommended checklist for hygienic operation and the maintenance of air-handling systems
Activity
Outside air/expelled air apertures
Chamber internals/appliance casing
Check for contamination, damage and
corrosion
Air filter
Check for excessive contamination and
damage (leaks)
Steam humidifier
Wash with cleaning agents
Rinse and dry the humidifier chamber,
disinfect if necessary
Check steam wand for deposits
Check hygiene condition
Heat exchanger
Check for contamination, damage and
corrosion
Check siphon function
Check hygiene condition
Fan
Check for contamination, damage and
corrosion
Heat recovery
Check condensate tray and mist
eliminator for contamination, corrosion
and function
Check siphon function
Check hygiene condition
Ductwork and attenuator
Check for contamination, damage and
corrosion
End units
Check end units with outside air filter for
contamination
Check heat exchangers in end units
without air filters for contamination
Replace air filters
Genuine WOLF spare parts can be ordered at short notice by faxing the requisite
information, accompanied by the order number (see rating plate) to this number:
+49 8751/74-1574.
3062049_201610

Checklist

Possible measure
Clean and repair
Change the air filters concerned if
the last change was not more than 6
months ago, otherwise change the
entire filter stage
Clean
Clean and repair
Repair
Clean and repair
Repair
Repair
Clean and repair
Replace air filters, clean appliance
Clean (vacuum cleaner)
KG Top
Months
12
3
6
6
6
3
3
6
6
3
3
12
12
3
6
12
33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kgw top

Table of Contents