Monarch NICE 5000 User Manual page 94

Integrated elevator controller
Table of Contents

Advertisement

5 System Commissioning and Functions
Figure 5-10 Wiring of the independent contactor + Relay NC contact
Safety
contactor
R
Three-phase AC
S
power supply
T
The parameter setting in such wiring mode is described in the following table.
Table 5-4 Parameter setting under the shorting PMSM stator scheme
Function
Parameter Name
Code
F5-18
X18 function selection
F5-34
Y3 function selection
Elevator function
F6-10
selection 2
5.5.2 Parallel Control of Two Elevators
The NICE5000 supports parallel control of two elevators, which is implemented by using
the CANbus communication port for information exchange and processing between the two
elevators.
The parallel control function has the following features:
When hall calls are registered, the system calculates the response time of the elevators
in parallel control in real time (based on distance, elevator arrival, door open/close), and
responds to all calls in the optimum way, minimizing the passenger waiting time.
The elevators are configured as the master and slave ones. When they have the same
response conditions, the system instructs the master or slave to respond a call based
on the random function.
The parallel control function considers the call response time, elevator use efficiency,
and in-car passenger waiting time. It avoids use ratio imbalance of elevators,
Regen. resistor
X18
+
– BR
U
V
W
NICE5000
MCTC-PG
Y1
Y1
M1
M1
Y2
M2
Y3
M3
Y4
M4
Y3
Y5
M5
Y6
M3
M6
FX: Contactor for shorting PMSM stator
SW: RUN contactor
Value
Allocate X18 with "Input of shorting PMSM
30
stator feedback signal".
Allocate Y3 with "Output of shorting PMSM
12
stator contactor feedback signal".
Bit8 = 0: NC output contactor
-
Bit8 = 1: NO output contactor
- 92 -
NICE5000 User Manual
FX
1
2
3
4
SW
1
2
3
4
5
6
Encoder
Shield
C
R
FX
SW
Safety circuit
5
6
C
R
FX
110 VAC
Description
24V
Motor
M