Siemens SCALANCE M800 Operating Instructions Manual page 12

Simatic net industrial remote communication remote networks
Hide thumbs Also See for SCALANCE M800:
Table of Contents

Advertisement

Security recommendations
● Factory setting
– Open
– Closed
● Authentication
Specifies whether or not the protocol is authenticated during access.
Protocol
Protocol/port
number
SSH
TCP/22
SFTP
HTTP
TCP/80
HTTPS
TCP/443
SNTP
UDP/123
SNMP v1/v3
UDP/161
DNS server
TCP/53
DNS client
UDP/53
Syslog
UDP/514
IPsec/IKE
UDP/500
UDP/4500
DHCP server
UDP/67
DHCP Client
UDP/68
NTP client
UDP/123
NTP server
UDP/123
Siemens Remote
TCP/443
Service
(cRSP/SRS)
PROFINET
UDP/34964
OpenVPN to
TCP, UDP
SINEMA RC
depending
on server
config [only
with Key-
Plug]
12
The factory setting of the port is "Open".
The factory setting of the port is "Closed".
Port status
Open
(when configured)
Open
(when configured)
Open
Open
(only outgoing)
Open
(when configured)
Open
(when configured)
Open
(when configured)
Open
(only outgoing)
Open
(when configured)
Open
(when configured)
Open
(when configured)
Open
(only outgoing)
Open
Open
(only outgoing)
Open
Open
(only outgoing)
Default port status
Local access
External
access
Open
Closed
Open
Closed
Open
Closed
Closed
Closed
Open
Closed
Open
Closed
Open
Closed
Closed
Closed
Closed
Open
Open
Closed
Open
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Open
Open
Closed
Closed
Operating Instructions, 08/2018, C79000-G8976-C331-08
Authentication
Encryption
Yes
Yes
Yes
No
Yes
Yes
No
No
Yes
Yes (when con-
figured)
No
No
No
No
No
No
Yes
Yes
No
No
No
No
No
No
No
No
Yes
Yes
No
No
Yes
Yes
SCALANCE M874, M876