Baxi Combi 224 Installation And Service Manual page 33

High efficiency wall hung condensing gas boiler
Hide thumbs Also See for Combi 224:
Table of Contents

Advertisement

Tab.23
Terminal position with minimum distance
Key
Description
A
Directly below an opening, air brick open­
(1)
ing window etc.
B
Above an opening, air brick, opening win­
(1)
dow etc.
Horizontally to an opening, air brick,
C
(1)
opening window etc.
D
Below gutters, soil pipes or drain pipes
(2)
E
Below eaves
(2)
Below balconies or car port roof
F
(2)
G
From a vertical drain pipe or soil pipe
(2)
H
From an internal or external corner
(2)
I
Above ground, roof, or balcony level
(1) In addition, the terminal should be no nearer than 150mm to an opening in the building fabric formed for the purpose of accommodating
a built-in element such as a window frame.
(2) Only ONE 25mm clearance is allowed per installation. If one of the dimension D,E,F,G or H is 25mm then the remainder MUST be as
shown in brackets, in accordance with BS 5440–1.
Fig.20
Property boundary
A*
2
3
7696317 - 1 - 21032018
If the terminal discharges onto a pathway or passageway, check that
combustion products will not cause a nuisance and that the terminal will
not obstruct the passageway.
If a terminal is less than 2 metres above a balcony, above ground or
above a flat roof to which people have access, then a suitable terminal
guard must be provided.
1
2
3
A
*Reduction to the boundary is possible down to 25mm but the flue
deflector must be used.
1
PN-0000457
mm
Key
Description
300
J
From a surface or boundary line facing
a terminal
300
K
From a terminal facing a terminal
(Horizontal flue)
From a terminal facing a terminal (Ver­
tical flue)
300
L
From an opening in carport (e.g. door,
window) into the dwelling
25 (75)
M
Vertically from a terminal on the same
wall
25 (200)
N
Horizontally from a terminal on the
same wall
25 (200)
R
From adjacent wall to flue (vertical on­
ly)
25 (150)
S
From an adjacent opening window
(vertical only)
25 (300)
T
Adjacent to windows or openings on
pitched and flat roofs
300
U
Below windows or openings on pitch­
ed roofs
Important
Under car ports we recommend the use of the plume
displacement kit. The terminal position must ensure the safe and
nuisance - free dispersal of combustion products.
Property boundary line
Terminal assembly
Top view rear flue
300mm minimum*
Important
The distance from a fanned draught appliance terminal installed
parallel to a boundary may not be less than 300mm in accordance
with the diagram opposite.
5 Before installation
mm
600
1200
600
1200
1500
300
300
1000
600
2000
33