[2-10 Restrictions on Refrigerant Pipes ]
(2) P144 - P360 models
The figure shows a system with three outdoor units. (P264-P360 models)
Outdoor unit Outdoor unit
Outdoor unit
A
B
C
Second gas refrigerant distributor
Second liquid refrigerant distributor
First liquid refrigerant distributor
First gas refrigerant distributor
First branch
Length
Between outdoor units
Total pipe length
Total pipe length (L) from the outdoor unit to the
farthest indoor unit
Total pipe length from the first branch to the far-
thest indoor unit ( )
Height
Between indoor and outdoor units
difference
Between indoor units
Between outdoor units
*1. If the piping length exceeds 40 meters (but does not exceed 90 meters), use one-size larger pipes for indoor unit
liquid pipes.
*2. If the height difference between indoor units exceeds 15 meters (but does not exceed 30 meters), use one-size
larger pipes for indoor unit liquid pipes.
HWE14080
Note1 Install the pipe that connects the branch pipe and the outdoor units in
the way that it has a downward inclination toward the branch pipe.
Downward inclination
D
Upward inclination
L
(Note)
E
F
G
I
a
b
Indoor
Indoor
Indoor
1
2
J
K
M
e
f
Indoor
Indoor
Indoor
5
6
Operation
- 45 -
Provide a trap on the pipe (gas pipe only) within 2 m from the
joint pipe if the total length of the pipe that connects the joint
pipe and the outdoor unit exceeds 2 m.
To indoor unit
2m [6ft]
To indoor unit
c
d
E
Indoor
Note : "Total sum of downstream unit model numbers"
3
4
in the table is the sum of the model numbers
of the units after point E in the figure.
g
i
Indoor
7
8
Pipe sections
A+B+C+D
A+B+C+D+E+F+G+I+J
+K+M+a+b+c+d+e+f+g
+i
A(B)+C+E+J+K+M+i
F+G+I+d or J+K+M+i
H
h1
h2
To indoor unit
Joint pipe
Trap
(gas pipe
only)
To indoor unit
2m [6ft] Max.
Joint pipe
To downstream units
Unit: m [ft]
Allowable length of
pipes
10 [32] or less
1000 [3280] or less
165 [541] or less
(Equivalent length 190
[623] or less)
*1
40 [131] or less
50 [164] or less
(40 [131] or below if
outdoor unit is below in-
door unit)
*2
15 [49] or less
0.1[0.3] or less