[5-2 Outdoor Unit Control ]
(2) P144, P168, P192, P216, P240 models
Initial startup mode starts.
The compressor on the OC starts up.
F
60Hz
The total operating load of the indoor unit
after 5 minutes of operation is P96 or above.
The compressor on the OC remains in operation, and the
compressor on the OS starts up.
50
F
60Hz (both OC and OS)
Completed in the integrated operation time of 35 minutes.
or
F < 50Hz (both OC and OS)
Completed in the integrated operation time of 90 minutes.
or the discharge superheat (TH4 - Tc) is detected (within
5 minutes of startup) that remains above approximately
25 degrees for one minute .
Initial startup mode complete
1
Qj:Total capacity (models) code
For the capacity code, refer to the following table.
Model
Capacity (model) code
HWE14080
(*1 Qj
50)
Yes
P06
P08
P12
4
5
6
No
The compressor on the OC starts up.
*2
50
F
60Hz (OC)
Completed in the integrated operation time of 35 minutes.
or
F < 50Hz (OC)
Completed in the integrated operation time of 90 minutes.
or the discharge superheat (TH4 - Tc) is detected (within
5 minutes of startup) that remains above approximately
*3
25 degrees for one minute .
Both the OC and OS stop.
The startup sequence of the OC and OS is rotated.
The compressor on the OS starts up.
50
F
60Hz (OS)
Completed in the integrated operation time of 35 minutes.
or
F < 50Hz (OS)
Completed in the integrated operation time of 90 minutes.
or the discharge superheat (TH4 - Tc) is detected (within
5 minutes of startup) that remains above approximately
25 degrees for one minute .
*2
The air conditioning load is too small for both the OC and the OS to
simultaneously stay in operation.
*3
The air conditioning load is high enough for both OC and OS to
simultaneously stay in operation.
P15
P18
P24
8
10
13
- 101 -
P27
P30
P36
14
16
20
P48
25
GB