Viessmann Vitocrossal 300 Series Technical Data Manual page 17

For operating with natural gas and liquid propane gas
Hide thumbs Also See for Vitocrossal 300 Series:
Table of Contents

Advertisement

Vitocrossal 300 CU3A 26 to 199 Technical Data
Accessories for Vitocrossal 300 CU3A
Low-Loss Header (continued)
Principle of Operation
Legend
T1
Boiler supply temperature
T2
Boiler return temperature
T3
System supply temperature
T4
System return temperature
Vprimary
Boiler circuit flow rate
Vsecondary
Heating circuit flow rate
Vbypass
Bypass flow rate
Qprimary
Heat supplied by boiler
Qsecondary
Heat consumed by system
IMPORTANT
When installing a low-loss header, the system mixed
supply temperature (T3) must be calculated as follows:
Vprimary < Vsecondary
T1 > T3
T2 = T4
Qprimary = Qsecondary
T1 167°F (75°C)
Vsecondary=Vprimary+Vbypass
Model No.
Type 80/60
Type 120/80
Type 160/80 *1
Type 200/120 *1
*1 Floor-mounted version (typically used for
multiple-boiler installations).
Neutralization Unit for Single-Boiler Applications
with neutralizing granulate
for models CU3A 26, 35, 94, 125
for models CU3A 45, 57, 160, 199
Neutralization Pellets
for models CU3A 26 to 199
2 x 1.3 kg for refill or replacement purposes
Accessories
Max. system flow rate
17.6 USGPM (4 m
3
/h)
35.2 USGPM (8 m
3
/h)
44 USGPM (10 m
3
/h)
80 USGPM (18 m
3
/h)
17