Mitsubishi Electric PUHZ-ZRP35VKA Service Manual page 91

Hide thumbs Also See for PUHZ-ZRP35VKA:
Table of Contents

Advertisement

SW2 setting
DC bus voltage
150 – 400 (ZRP35 – 140V)
ON
300 – 750 (ZRP100 – 140Y)
1
2 3 4 5 6
Capacity save
0 – 100
When air conditioner is connected to
ON
M-NET and capacity save mode is
demanded, "0"~"100" is displayed.
1
2 3 4 5 6
When there is no setting
of capacity save "100" is
displayed.
Error postponement code history (2)
ON
of outdoor unit
1
2 3 4 5 6
Error postponement code history (3)
of outdoor unit
ON
1
2 3 4 5 6
Error code history (3) (Oldest)
ON
Alternate display of abnormal unit
number and code.
1
2 3 4 5 6
Error thermistor display
ON
When there is no error thermistor,
"–" is displayed.
1
2 3 4 5 6
Operation frequency on error occurring
0 – 255
ON
1
2 3 4 5 6
Fan step on error occurring
0 – 10
ON
1
2 3 4 5 6
Outdoor pipe temperature(TH33)
ON
-39 – 88
1
2 3 4 5 6
OCH527B
Display detail
91
The black square ( ) indicates a switch position.
Explanation for display
150 – 400 (RP35 – 140V)
300 – 750 (RP100 – 140Y)
(When it is 100V or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
0 – 100
(When the capacity is 100% hundreds digit, tens digit
and ones digit are displayed by turns.)
(Example) When 100%;
0.5 secs.
Postponement code display
Blinking: During postponement
Lighting: Cancellation of postponement
"00" is displayed in case of no postponement.
Postponement code display
Blinking: During postponement
Lighting: Cancellation of postponement
"00" is displayed in case of no postponement.
When no error history, "0" and "– –" are displayed by
turns.
3: Outdoor pipe temperature /Liquid (TH3)
6: Outdoor pipe temperature /2-phase (TH6)
7: Outdoor outside temperature (TH7)
8: Outdoor heatsink (TH8)
0~255
(When it is 100Hz or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
(Example) When 125Hz;
0.5 secs.
0 – 10
-39 – 88
(When the temperature is 0: or less, "–" and
temperature are displayed by turns.)
0.5secs.
2 secs.
1
00
0.5secs.
2 secs.
1
25
Unit
V
%
Code
display
Code
display
Code
display
Code
display
Hz
Step
°C