Vitodens 200-W B2HA 80 to 100, 285 to 352 Installation
Technical Data
(continued)
Boiler Model No. B2HA
Dimensions
Overall depth
Overall width
Overall height
Flue gas *6
Temperature (at boiler return
temperature of 86ºF (30ºC)
- at rated full load
- at rated partial load
Temperature (at boiler return
temperature of 140ºF (60ºC)
Max. condensate flow rate *7
for NG and LPG
T
/T
=104/86ºF (40/30ºC)
S
R
Condensate connection *8
Boiler flue gas connection *9
Combustion air supply connection
(coaxial)
Sound Rating
- at maximum input
- at minimum input
*A
For high altitude installations 5,000 - 10,000 ft. (1500 m - 3000 m), the input for model B2HA 100, 352 will have an
altitude de-ration of 14% for 5,000 ft. (1500 m) and 29% for 10,000 ft. (3000 m) average of 2.8% / 1,000 ft. (305 m).
*6
Measured flue gas temperature with a combustion air temperature of 68°F (20°C).
*7
Based on maximum input rate.
*8
Requires 1 inch (25 mm) tubing. See the Installation Instructions of the Vitodens 200-W, B2HA for details.
*9
For side wall vent installations (coaxial system):
Do not exceed max. equivalent length specified in the Installation Instructions of the Vitodens 200-W, B2HA
Venting System.
Vitodens 200-W B2HA 80 to 100, 285 to 352 boilers can only be common vented with other Vitodens 200-W
boilers of the same size.
Side wall co-axial vent installation must include Viessmann protective screen!
For details refer to the Installation Instructions for the Vitodens 200-W, B2HA Venting System.
*10 Add approximately 2b inches (65 mm) for coaxial vent pipe transition adaptor.
For information regarding other Viessmann System Technology componentry, please reference the documentation
of each respective product.
Note: For high altitude installation at 10,000 ft. the input for model B2HA 19 to 80, 68 to 285 will have an altitude de-ration
of 21%.
80, 285
inches
21
(mm)
(530)
inches
19
(mm)
(480)
inches
43½
(mm)
(850)
ºF (ºC)
95 (35)
ºF (ºC)
91 (33)
ºF (ºC)
149 (65)
USG/h
2.77
(L/h)
(10.5)
hose nozzle
Ø in.
¾-
Ø
in. (mm)
4
/
(110)
3
8
outer
Ø in. (mm)
6 (150)
dB
56
dB
38
88, 311 *A
21
(530)
19
(480)
43½
(1105)
135 (57)
99 (37)
162 (72)
3.1
(11.7)
¾-
1
1
4
/
(110)
3
8
6 (150)
69
38
Additional Information
100, 352 *A
21
(530)
19
(480)
43b
*10 (1105)
135 (57)
99 (37)
162 (72)
3.5
(13.1)
¾-
1
4
/
(110)
3
8
6 (150)
69
38
61