1-3 Other Component Specifications
MODEL No.
Power Transformer
Rated
Primary
Secondary
Coil resistance
Thermal cut off temperature
Thermistor (Coil sensor)
Coil resistance
Thermistor (Room or coil sensor)
Coil resistance
Relay
Coil rated
Contact rating
Coil resistance (at 25 °C)
Solenoid control valve or coil
Solenoid control valve
Solenoid coil
Float switch
Rated (Contact rated)
Indoor Unit
SPW-D363GH56
SPW-D483GH56
ATR - II215TB
V. Hz
AC 230 V, 50 Hz
10.2V , 1.4 A
14 V , 0.5 A
Ω
WHT – WHT : 110 , BRN – BRN : 0.5 WHT – WHT : 300 , BRN – BRN : 2.2
RED – RED : 2.3
°C
145
PBC - 41E - S36, PBC - 41E - S25, PBC - 41E - S4
–10 °C : 23.7
kΩ
–5 °C : 18.8
0 °C : 15.0
5 °C : 12.1
KTEC - 35 - S2
0 °C : 16.5 , 40 °C :
kΩ
5 °C : 12.8 , 45 °C :
10 °C : 10.0 , 50 °C :
20 °C :
6.3 , 55 °C :
30 °C :
4.0
—
V
—
V.A
—
Ω
—
HKV - 30D16
EKV - MOZS559E0
FS - 3502 - 204
AC 230 V, 50 W
– 19 –
1. Specifications
1. Specifications
Outdoor Unit
SPW-C363GH8
ATR - I65B
AC 230 V, 50 Hz
14 V , 0.4 A
—
145
10 °C : 9.7
,
20 °C : 6.5
,
30 °C : 4.4
,
40 °C : 3.1
,
45 °C : 2.6
PTC - 51H - S1
60 °C : 13.8
, 90 °C :
2.7
70 °C :
, 100 °C :
2.2
9.7
75 °C :
, 110 °C :
1.8
8.2
80 °C :
, 120 °C :
1.5
7.0
85 °C :
, 130 °C :
5.9
FMCA - 1SZ607
AC 220 - 240 V
AC 440 V, 13 A
—
CHV - 0301
CHV - 01AJ504D1
—
—
SPW-C483GH8
1
1
5.1
3.8
2.8
2.2
1.7
CHV - 0401
SM830036