Daikin Altherma 3 R F Installer's Reference Manual page 226

Hide thumbs Also See for Altherma 3 R F:
Table of Contents

Advertisement

11
|
Configuration
Installer reference guide
226
#
[9.9.3]
[5-05]
Limits when [9.9.1]=Inputs and [9.9.2]=Amp:
#
[9.9.4]
[5-05]
[9.9.5]
[5-06]
[9.9.6]
[5-07]
[9.9.7]
[5-08]
Limit when [9.9.1]=Continuous and [9.9.2]=kW:
#
[9.9.8]
[5-09]
Limits when [9.9.1]=Inputs and [9.9.2]=kW:
#
[9.9.9]
[5-09]
[9.9.A]
[5-0A]
[9.9.B]
[5-0B]
[9.9.C]
[5-0C]
Priority heater
This setting defines the priority of the electrical heaters depending on applicable
limitation. As no booster heater is present, the backup heater will always be
prioritised.
#
[9.9.D]
[4-01]
BBR16
See
"6.6.4  BBR16 power
functionality.
INFORMATION
Restriction: BBR16 settings are only visible when the language of the user interface is
set to Swedish.
Code
Limit: Only applicable in case of full time
current limitation mode.
0 A~50 A
Code
Limit 1: 0 A~50 A
Limit 2: 0 A~50 A
Limit 3: 0 A~50 A
Limit 4: 0 A~50 A
Code
Limit: Only applicable in case of full time
power limitation mode.
0 kW~20 kW
Code
Limit 1: 0 kW~20 kW
Limit 2: 0 kW~20 kW
Limit 3: 0 kW~20 kW
Limit 4: 0 kW~20 kW
Code
Priority heater:
0 None : The backup heater is prioritised.
1 Booster
setting will be reverted back to 0=None and
the backup heater will be prioritised.
2 Backup
prioritised.
4
limitation"  [
  61] for detailed information about this
Description
Description
Description
Description
Description
heater: After restart, the
heater: The backup heater is
ERLA11~16DAV3+W1 + EBVH16SU23DJ
Daikin Altherma 3 R F
4P655196-1 – 2021.09