Burner adjustment RS4D - RS5D - RS5D TL - RS5DF

5.7.1

Combustion head adjustment

The ignition should occur at a low output and not higher than 120 kW.
In order to measure the ignition output:
 disconnect the connector (CN1) on the ionisation probe
cable (see paragraph "Electrical system carried out by
the factory" on page 22); The burner comes on and goes
into lockout after the safety time (3s).
 Perform 10 ignitions with consecutive lockouts.
 Read the total quantity of gas burned on the meter.
This quantity must be equal to or lower than:
3
0.10 Nm
for G20 (natural gas H)
3
0.10 Nm
for G25 (natural gas L)
3
0.03 Nm
for G31 (LPG).
It depends on the burner output and is carried out by turning the
adjusting screw 6)(Fig. 13) clockwise or anti-clockwise until the
notch marked on the regulating rod 2)(Fig. 13) lines up with the
outer surface of the head assembly 1)(Fig. 13).
SW1019
5.7.2

Removing the head assembly

To remove the head assembly (Fig. 13) it is necessary to:
 disconnect the connections 3) and 5);
 remove the tube 4) and loosen the screws 8);
 unscrew and remove the screws 7), remove the head holder
assembly 1) applying a slight rotation to the right.
Take care not to change the setting position on
the elbow-bracket (2)(Fig. 13) when dismantling.
CAUTION
Installation
5.7.3

Reassembling the head assembly

Reassemble with the reverse procedure to that described above,
repositioning the head assembly 1)(Fig. 13) as it was originally.
Screw in the screws 7)(Fig. 13) all the way without
locking them.
Lock them with a tightening torque of 3 - 4 Nm.
CAUTION
Check that when operating there are no gas leaks
from the screw housings.
If the pressure test point (11) should become
slack accidentally(Fig. 13) we recommend fixing it
WARNING
correctly ensuring that the hole (F)(Fig. 13) inside
the head assembly 1)(Fig. 13) is facing down-
wards.
In (Fig. 14) the head is adjusted to an output of about 230 kW.
The notch 4 of the regulating rod lines up with the outer surface
of the head assembly as shown in the diagram.
Example:
The burner is installed in a 210 kW boiler.
Considering an efficiency of 90% the burner should deliver about
230 kW.
The diagram shows that for this output the adjustment must be
made on notch 4.
NOTE:
The diagram is for indication purposes; to ensure the burner
works at peak performance we suggest adjusting the com-
bustion head according to the requirements requested by
the type of boiler.
kcal/h
kW
350
290,000
330
270,000
310
250,000
290
270
230,000
250
210,000
230
190,000
210
170,000
190
150,000
170
130,000
150
Fig. 13
130
110,000
110
Set point
17
GB
0
2
4
6
20183748
8
10
Fig. 14