True GDM-26-LD Installation Manual page 28

Table of Contents

Advertisement

TRUE
GLASS DOOR MERCHANDISERS
LAE CONTROLLER PARAMETER SETTINGS FOR CELSIUS
For LAE control model AR2-28 ONLY, ALL parameters with a formula
shown need to be converted for Celsius applications.
EXAMPLE:
If current SPL is set for 20 degrees F the formula is (X-32) / 1.8
(20-32) / 1.8 = -6.7 Celsius
27
AR2-28
SCL
1C
SPL
(X-32) / 1.8
SPH
(X-32) / 1.8
SP
(X-32) / 1.8
C-H
HYS
(X) / 1.8
CRT
CT1
CT2
CSD
DFM
DFT
DH1
DH2
DH3
DH4
DH5
DH6
DLI
(X-32) / 1.8
DTO
DTY
DPD
DRN
DDM
DDY
FID
FDD
(X-32) / 1.8
(X-32) / 1.8
(X-32) / 1.8
FTO
FCM
FDT
(X) / 1.8
(X) / 1.8
(X) / 1.8
FDH
FDH
FDH
(X) / 1.8
(X) / 1.8
(X) / 1.8
FT1
FT1
FT1
FT2
FT2
FT2
FT3
FT3
FT3
ATM
ATM
ATM
ALA
(X-32) / 1.8
AHA
(X-32) / 1.8
ALR
(X) / 1.8
AHR
(X) / 1.8
ATI
ATD
.
.
WWW
TRUEMFG
COM
ADO
AHM
AHT
(X-32) / 1.8
ACC
IISM
IISL
(X-32) / 1.8
IISH
(X-32) / 1.8
IISP
(X-32) / 1.8
IIHY
(X) / 1.8
IIFC
HDS
IIDF
SB
DS
DSM
DI2
STT
STT
STT
EDT
EDT
EDT
LSM
LSM
LSM
OA1
OA1
OA1
OA2
OA2
OA2
CD
INP
OS1
(X) / 1.8
T2
OS2
(X) / 1.8
T3
OS3
(X) / 1.8
TLD
TDS
AVG
SIM
ADR