Cooling module for domestic heat pump (Genesis
platform), Passive and Passive/Active
www.heating.danfoss.com

Advertisement

Table of Contents
loading

Summary of Contents for Danfoss Genesis Passive

  • Page 1 MAKING MODERN LIVING POSSIBLE Installation Guide Cooling module for domestic heat pump (Genesis platform), Passive and Passive/Active www.heating.danfoss.com...
  • Page 2 Danfoss A/S is not liable or bound by warranty if these instructions are not adhered to during installation or service. The English language is used for the original instructions. Other languages are a translation of the original instructions. (Directive 2006/42/EC)
  • Page 3: Table Of Contents

    ..... . Electrical Wiring Cooling Module Passive/Active 230 V ....Danfoss Heating Solutions VIMAB102...
  • Page 4: About Documents And Decals

    Component, ordinary delivery according to proposed system solutions Components, accessories according to proposed system solutions 1.1.3 Pipe connections Tap water Water heater Temperature and pressure relief valve Heating system Brine system Expansion tank with safety valve, brine Air bleeding VIMAB102 Danfoss Heating Solutions...
  • Page 5: Important Information/Safety Instructions

    Installation and connection should be carried Caution out in accordance with the instructions, in or- der to avoid subjecting local residents to noise disturbance. Danfoss Heating Solutions VIMAB102...
  • Page 6 It is important that the heating and brine cir- cuits are completely bled after installation. Bleed valves must be installed where necessa- Only spare parts approved by Danfoss Värme- Caution pumpar may be used for this appliance. VIMAB102...
  • Page 7: Electrical Connection

    The installation may only be commissioned if Caution the heating system, water heater and brine system have been filled and bled. Otherwise the circulation pumps can be damaged. Danfoss Heating Solutions VIMAB102...
  • Page 8: Area Of Use

    The cooling modules make it possible to retain either passive or passive/active cooling from the rock –ground- water collectors. The distribution system for this can be the radiator system (fan coils) or under floor heating systems. Cooling starts when the outside temperature exceeds the set value for seasonal stop. VIMAB102 Danfoss Heating Solutions...
  • Page 9: Installation

    Cooling module Pipe installation is carried out according to the dia- Fan coils grams. Expansion card Heat pump Ground source Position Name Brine line out 1 Brine line in 1 Cooling supply line Cooling return line Danfoss Heating Solutions VIMAB102...
  • Page 10: Dimensions And Connections, Passive/Active

    Name Brine line out 1 Brine line in 1 Brine line out 2 Brine line in 2 Supply line heating system Heating system supply line heat pump Return heating system Cooling supply line Cooling return line VIMAB102 Danfoss Heating Solutions...
  • Page 11: Electrical Installation

    Check if terminal block "X2" is mounted in the heat pump. If not, mount the terminal block that comes with the cooling module as followed. 1 Turn of the power. 2 Check if terminal block "X2" is mounted in the heat pump. 3 Snap block in to place. Danfoss Heating Solutions VIMAB102...
  • Page 12 Cooling module (with factory connected Expansion card) Heat Pump (Domestic) If the cooling module shall be able to produce cooling and heating at the same time, it is recommended that a system supply line sensor is installed on the heating circuit. VIMAB102 Danfoss Heating Solutions...
  • Page 13: Configuration In The Control System

    6. Press on the text Cooling. 7. Enable passive and/or active cooling depending on what unit the end customer have. 8. Ability to change the seasonal cooling tempera- ture. Factory settings: 25 9. Confirm settings by pressing Danfoss Heating Solutions VIMAB102...
  • Page 14: Function During Cooling Operation

    These two combined with time creates a cooling season integral. When the integral reaches the start-/stop lim- it cooling season begins/ends. (From software 5.01) ▪ Start limit cooling season integral: ≥100 (Upper limit: 300) ▪ Stop limit cooling season integral: ≤-100 (Lower limit: -300) VIMAB102 Danfoss Heating Solutions...
  • Page 15 Example. Start temperature = 18°C, Stop temperature = 15°C. 1. Active cooling start (Start temperature cooling) 2. Passive cooling start (Calculated) 3. Active cooling stop (Calculated) 4. Passive cooling stop (Stop temperature cooling) ° C 17,25 15,75 Danfoss Heating Solutions VIMAB102...
  • Page 16: External Available Pressure

    Installation Guide Cooling module for domestic heat pump (Genesis platform), Passive and Passive/Active External available pressure External available pressure, Passive, H–J External available pressure, Passive External available pressure (kPa) Flow (l/s) VIMAB102 Danfoss Heating Solutions...
  • Page 17: External Available Pressure, Passive/Active H-J

    Installation Guide Cooling module for domestic heat pump (Genesis platform), Passive and Passive/Active External available pressure, Passive/Active H-J External available pressure, Passive External available pressure (kPa) Flow (l/s) Danfoss Heating Solutions VIMAB102...
  • Page 18: Cooling Module, Heating

    Cooling module for domestic heat pump (Genesis platform), Passive and Passive/Active Cooling Module, Heating J H E Position Name Cooling circuit Heat exchanger (accessory) Cooling module Passive / Active Brine in Brine out Supply line Return line Hot water Cold water Expansion VIMAB102 Danfoss Heating Solutions...
  • Page 19: Cooling Module, Passive Mode

    Cooling module for domestic heat pump (Genesis platform), Passive and Passive/Active Cooling Module, Passive mode J H E Position Name Cooling circuit Heat exchanger (accessory) Cooling module Passive / Active Brine in Brine out Supply line Return line Hot water Cold water Expansion Danfoss Heating Solutions VIMAB102...
  • Page 20: Cooling Module, Active Cool Mode

    Passive and Passive/Active Cooling Module, Active cool mode J H E Position Name Cooling circuit Heat exchanger (accessory) Cooling module Passive / Active Brine in Brine out Supply line Return line Hot water Cold water Expansion VIMAB102 Danfoss Heating Solutions...
  • Page 21: Internal Wiring Diagram

    Installation Guide Cooling module for domestic heat pump (Genesis platform), Passive and Passive/Active Internal wiring diagram Electrical Wiring Cooling Module Passive 230 V 201.7 Installation connections 201.9 201.1 202.1 202.2 MBa+ BU/WH MBa- Installation connections SGND Danfoss Heating Solutions VIMAB102...
  • Page 22: Electrical Wiring Cooling Module Passive/Active 230

    Installation Guide Cooling module for domestic heat pump (Genesis platform), Passive and Passive/Active Electrical Wiring Cooling Module Passive/Active 230 V 201.7 Installation connections 201.9 201.1 201.2 201.3 202.1 202.2 208.1 208.8 MBa+ BU/WH MBa- Installation connections SGND VIMAB102 Danfoss Heating Solutions...
  • Page 23 Installation Guide Cooling module for domestic heat pump (Genesis platform), Passive and Passive/Active Danfoss Heating Solutions VIMAB102...
  • Page 24 Internet: www.heating.danfoss.com Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies.