APPROVALS

Approvals:
Underwriters Laboratories Inc:
Remote bulb devices and well-mounted devices shipped without well are component recognized:
File No. MP466, Guide No. MBPR2.
L4006A shipped with well, L4006G, L4007A,B; L6006C for surface mounting, L6006B for direct immersion mounting, and
L6007A are listed: File No. MP466, Guide No. MBPR.
L6008G is listed: File No. E4436, Guide No. XAPX Canadian Standards Association: File No. LR1620, Guide No. 400-E-O.
ANSI Miswiring: Models with 1/4 in. (6.35 mm) tab terminal meet ANSI Appliance Miswiring Standard.
Finish: Gray.
ACCESSORIES AND PARTS
Accessories and Parts:
137536A Scale Lock Assembly: Includes one 137536-767 Scale Lock and one 80844C-767 Screw, No. 3-48 x 3/16 (5 mm).
Q615A1004 Weatherproof Enclosure (for remote bulb devices only).
107408 Heat-Conductive Compound (4-oz. can).
104488 Spring Clip (stainless steel).
124904 Well Adapter.
Immersion Well Assemblies and Compression Fittings:
See form no. 68-0040, Wells and Fittings for Temperature Controllers, for list and ordering information

INSTALLATION

When Installing This Product
1
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check product operation
as provided in these instructions.
WARNING
Explosion Hazard.
Can cause serious injury, death or property
damage. This product is intended for use only
in systems with a pressure relief valve.
WARNING
Electrical Shock Hazard.
Can cause serious injury or death. Disconnect
power supply before beginning installation to
prevent electrical shock or equipment dam-
age.
CAUTION
Equipment Damage Hazard.
Use of incorrect device or improper installa-
tion can damage the system.
1. Do not replace immersion-type Aquastat
Controller with strap-on Aquastat Controller.
2. Do not secure draw nut so tightly that
retainer clamp can collapse tubing.
60-2104—01
IMPORTANT
1. Terminals on these Aquastat relays are approved for
copper wire only.
2. Controller may be used with or without immersion well. If
used, well must snugly fit sensing bulb for best thermal
response. Insert bulb until it rests against the bottom of
the well. Use well of correct length and bend the tubing,
if necessary, to provide enough force to hold the bulb
against the bottom of the well. Avoid making a sharp
bend in the tubing as it can produce a break in the
tubing and cause loss of fill. This condition causes the
High and Low Limit controls to be made continuously.
3. If well does not snugly fit on bulb, use the heatconductive
compound, included with Super Tradeline and Tradeline
models, as follows: Fold the plastic bag of compound
lengthwise and twist gently. Snip the end of the bag
and insert into the well. Slowly pull out the bag while
squeezing firmly to distribute compound evenly in the
well. Insert the bulb into the well. Bend the tubing, if
necessary, to provide force to hold the bulb against the
bottom of the well and to hold the outer end of the bulb
firmly in contact with the side of the well. Wipe off excess
compound
The manufacturer usually provides a tapping for insertion
of the controller sensing element. This tapping is located at
a point where typical water temperature can be measured.
Depending on the model, the element is inserted in an
immersion well, through a boiler fitting, or directly immersed.
Installation should be made by a qualified service technician.
Follow the instructions furnished by the system manufaturer,
if available. Otherwise, refer to appropriate procedure listed
below.