Mitsubishi Electric CITY MULTI PUHY-400YMF-C Service Handbook page 189

Table of Contents

Advertisement

No
SW1
Item
12345678910
235
1101011100
IC12 Operation
Mode
236
0011011100
IC13 Operation
Mode
237
1011011100
IC14 Operation
Mode
238
0111011100
IC15 Operation
Mode
239
1111011100
IC16 Operation
Mode
240
0000111100
IC1 Filter
241
1000111100
IC2 Filter
242
0100111100
IC3 Filter
243
1100111100
IC4 Filter
244
0010111100
IC5 Filter
245
1010111100
IC6 Filter
246
0110111100
IC7 Filter
247
1110111100
IC8 Filter
248
0001111100
IC9 Filter
249
1001111100
IC10 Filter
250
0101111100
IC11 Filter
251
1101111100
IC12 Filter
252
0011111100
IC13 Filter
253
1011111100
IC14 Filter
254
0111111100
IC15 Filter
255
1111111100
IC16 Filter
256
0000000010
257
1000000010
258
0100000010
259
1100000010
260
0010000010
261
1010000010
262
0110000010
263
1110000010
264
0001000010
Indoor Unit Check
265
1001000010
266
0101000010
Indoor Unit
Operation Mode
267
1101000010
268
0011000010
Indoor Unit
Thermostat
269
1011000010
LD1
LD2
LD3
Unit No. 17
Unit No. 18
Unit No. 19
Unit No. 20
Unit No. 25
Unit No. 26
Unit No. 27
Unit No. 28
Unit No. 17
Unit No. 18
Unit No. 19
Unit No. 20
Unit No. 25
Unit No. 26
Unit No. 27
Unit No. 28
Unit No. 17
Unit No. 18
Unit No. 19
Unit No. 20
Unit No. 25
Unit No. 26
Unit No. 27
Unit No. 28
-186-
Display
LD4
LD5
LD6
LD7
0: Stop
1: Fan
2: Cooling
3: Heating
4: Dry
0000 ~ 9999
Unit No. 21
Unit No. 22
Unit No. 23
Unit No. 29
Unit No. 30
Unit No. 31
Unit No. 21
Unit No. 22
Unit No. 23
Unit No. 29
Unit No. 30
Unit No. 31
Unit No. 21
Unit No. 22
Unit No. 23
Unit No. 29
Unit No. 30
Unit No. 31
Variable capacity unit
Remarks
LD8
Lights up if an
Unit No. 24
abnormal stop has
occurred in the IC.
Unit No. 32
Unit No. 24
Lights up during
cooling.
Unit No. 32
Blinks during heating.
Goes off during stop
and blower operation.
Unit No. 24
Lights up when
thermostat is ON.
Unit No. 32
Goes off when
thermostat is OFF.

Advertisement

Table of Contents
loading

Table of Contents