Checking code
Meaning, detecting method
5101
Discharge
1 Detects thermistor short (high
(TH11)
temperature pick up) during
(TH12)
operation or open circuit (low
temperature pick up). The out-
5102
Low
d o o r u n i t i s t e m p o ra r i l y
Pressure
stopped and it enters the 3-
Satura-
minute restart prohibit mode.
tion (TH2)
If the temperature detected by
the thermistor immediately
Liquid
5103
before the restarting is within
Level
the normal range, the unit is
Detection
(TH3)
restarted.
2 If a short in the thermistor or
5104
Liquid
an open circuit is detected im-
Level
mediately before restarting, an
Detection
error stop is performed and
(TH4)
one of the following numbers
is displayed: 5101, 5102,
Liquid pipe
5105
5103, 5104, 5106, 5107, 5108
(TH5)
or 5109.
3 During the 3-minute restart
5106
Ambient
prohibit mode, the LED for the
Tempera-
error stop delay will be dis-
ture
(TH6)
played.
4 Short and open circuit detec-
Liquid
5107
tion is not performed for 10
Tempera-
minutes after the compressor
ture
has started operation, during
(TH7)
defrosting and for 3 minutes
after recovery from defrosting.
5108
Outlet SC
5 Open circuit detection for ther-
Coil
mistor TH11, 12 is not per-
(TH8)
formed immediately before
starting.
5109
Inlet SC
Coil
(TH9a)
CS circuit
(TH9b)
5112
Heat
Exchanger
Gas
(TH10a)
5113
Heat
Exchanger
Gas
(TH10b:
Variable
capacity unit)
Distribu-
tion pipe
tempera-
ture
(TH10b:
Constant
capacity unit)
5114
Compressur
shell
temperature
(TH10c)
Cause
1) Defective thermistor.
2) Tangled lead wires.
3) Broken covering.
4) Pin has come out of connector
creating connection deerror.
5) Broken wire.
6) Defective thermistor input on main
circuit board.
7) Thermistor mounting problem.
Short Detection
TH11, 12
240 C or more ( 0.57 k )
TH2
70 C or more ( 1.14 k )
TH3
70 C or more ( 1.14 k )
TH4
70 C or more ( 1.14 k )
TH5
110 C or more ( 0.4 k )
TH6
110 C or more ( 0.4 k )
TH7
110 C or more ( 1.14 k )
TH8
110 C or more ( 0.4 k )
TH9a, b
70 C or more ( 1.14 k )
THHS
TH10a
140 C or more ( 0.19 k )
(Variable Capacity Unit)
(Constant Capacity Unit)
TH10b
140 C or more ( 0.19 k )
(Variable Capacity Unit)
TH10b
110 C or more ( 0.4 k )
(Constant Capacity Unit)
TH10c
240 C or more ( 0.57 k )
(Variable Capacity Unit)
* The temperatures shown above and the detection ranges during operation.
When the unit is stopped, the ambient temperature will have an affect.
Therefore, compare the actual temperature and the monitor temperature
while making the determination.
-162-
Checking method & Countermeasure
Check thermistor resistance.
Check for tangled lead wires.
Checking for broken covering.
Check the connector for missing pins.
Check for broken wires.
Check pick up temperature using the
LED monitor. If there is a big difference
between that temperature and the ac-
tual temperature, replace the main cir-
cuit board.
Confirm that the thermistor is
mounted in the correct place.
Open Detection
15 C or less ( 321 k )
– 40 C or less ( 130 k )
– 40 C or less ( 130 k )
– 40 C or less ( 130 k )
– 40 C or less ( 130 k )
– 40 C or less ( 130 k )
– 40 C or less ( 130 k )
– 40 C or less ( 130 k )
– 40 C or less ( 130 k )
– 40 C or less ( 2.5 M )
– 40 C or less ( 130 k )
– 40 C or less ( 130 k )
– 40 C or less ( 130 k )
– 15 C or less ( 1.6 M )