Configuring the system
Adjusting set values

Set values for heating water buffer cylinder (HWB) and high temperature maintenance

Launch with
"Menu"
"Set val."
"HWB"
Fig. 13
The following settings can be changed:
"Heating water buffer cyl."
Set temperature for the heating water buffer cylinder
"Maintaining set val"
Set temperature for high temperature maintenance.
The value may be overridden by the application lim-
its.
"Htg limit"
If the average outside temperature (averaging over
24 hours) is lower than this value, the heating func-
tion for the heating water buffer cylinder is enabled.
20
(cont.)
"Start temp, heating water buffer cylinder"
If the temperature differential at the top of the heat-
ing water buffer cylinder is greater than this value,
the heating function for the heating water buffer cyl-
inder is switched on.
"Stop temp, compressor stage 1/2/3"
If the temperature at the bottom of the heating water
buffer cylinder reaches these differentials, the
respective stages are switched off.