9.4. Example 4. Change the VF-MB1/S15/AS3 parameter

When access to VF-MB1/S15/AS3 parameter, set "1000" to the PNU.
* This procedure changes the value of VF-MB1/S15/AS3 EEPROM.
9.4.1.
Write Request data table (Change, set 7 to VF-MB1/S15/AS3 parameter
Header DU0
Header DU1
Header DU2
Header DU3
Request Header (Byte 1)
Request Header (Byte 2)
Request Header (Byte 3)
Request Header (Byte 4)
Parameter Address (Byte 1)
Parameter Address (Byte 2)
Parameter Address (Byte 3)
Parameter Address (Byte 4)
Parameter Address (Byte 5)
Parameter Address (Byte 6)
Parameter Value (Byte 1)
Parameter Value (Byte 2)
Parameter Value (Byte 3)
Parameter Value (Byte 4)
* Refer to Appendix.
** Parameter number is fixed to 0x03E8 (1000) for accessing to VF-MB1/S15/AS3 parameter.
9.4.2.
Read Response data table (positive)
Header DU0
Header DU1
Header DU2
Header DU3
Request Header (Byte 1)
Request Header (Byte 2)
Request Header (Byte 3)
Request Header (Byte 4)
* Refer to Appendix.
9.4.3.
Read Response data table (negative, at set 256 to
Header DU0
Header DU1
Header DU2
Header DU3
Request Header (Byte 1)
Request Header (Byte 2)
Request Header (Byte 3)
Request Header (Byte 4)
Parameter Value (Byte 1)
Parameter Value (Byte 2)
Parameter Value (Byte 3)
Parameter Value (Byte 4)
* Refer to Appendix.
Field
Function number
Slot number (0)
Index (47)
Length
Request Reference
Request ID (0x02: Change) *
Axis
Number of Parameters
Attribute
Number of Elements
Parameter number, High byte **
Parameter number, Low byte **
VF-MB1/S15/AS3 Parameter number, High byte
VF-MB1/S15/AS3 Parameter number, Low byte
Format *
Number of Value
Value, High byte
Value, Low byte
Field
Function number
Slot number (0)
Index (47)
Length
Request Reference (mirrored)
Response ID *
Axis (mirrored)
Number of Parameters
Field
Function number
Slot number (0)
Index (47)
Length
Request Reference (mirrored)
Response ID *
Axis (mirrored)
Number of Parameters
Format * (= Error)
Number of Values
Error number, High byte *
Error number, Low byte *
Description
Description
f130
)
Description
- 43 -
E6581738④
f130
)
Value
0x5F
0x00
0x2F
0x0E
0x01
0x02
0x01
0x01
0x10
0x01
0x03
0xE8
0x01
0x30
0x42
0x01
0x00
0x07
Value
0x5E
0x00
0x2F
0x04
0x01
0x02
0x01
0x01
Value
0x5E
0x00
0x2F
0x08
0x01
0x82
0x01
0x01
0x44
0x01
0x00
0x02

Advertisement