Telegram 100: Vendor Specific - Toshiba TOSVERT VF-MB1 Function Manual

Hide thumbs Also See for TOSVERT VF-MB1:
Table of Contents

Advertisement

VF-AS3 profile
Scanner input c001 - c006
0: No action
1: fa06 (Communication command 1)
2: fa23 (Communication command 2)
3: fa07 (Frequency command, 0.01Hz)
4:fa33 (Torque command 0.01%)
5: fa50 (Terminal output data)
6: fa51 (Analog output(FM) data from comm.)
7: fa52 (Analog output(AM) data from comm.)
8: f601 (Stall prevention level, %)
9: f441 (Power running torque limit 1, level,0.01%)
10: f443 (Regenerative braking torque limit 1,
level 0.01%)
11: f460 (Speed loop proportional gain)
12: f461 (Speed loop stabilization coefficient)
13: acc (Acceleration time 1, 0.1s) *
14: dec (Deceleration time 1, 0.1s) *
15: ul
(Upper limit, 0.01Hz)
16: vb
(Torque boost value 1, 0.01%)
17: vlv
(Base frequency voltage 1, 0.1V)
acc
dec
* The unit of
,
fe76
** The unit of
*** The value which is transferred by the cyclic command transmission will not be stored to EEPROM.

7.1. Telegram 100: Vendor specific

The parameter access via PKW, and the transmission of two commands and monitors via
cyclic data are supported by Telegram 100.
PKW1
PKW2
PKW3
PKW4
Cyclic data 1
Cyclic data 2
is according to the parameter
,
fe77
is according to the parameter
PLC → INV
PKW1(PKE)
PKW2(IND)
PKW3(PWE1)
PKW4(PWE2)
c001
c002
Scanner output c021 - c026
0: No action
1: fd01 (Status information 1)
2: fd00 (Output frequency, 0.01Hz)
3: fd03 (Output current, 0.01%, With filter)
4: fd05 (Output voltage, 0.01%, With filter)
5: fc91 (Inverter alarm)
6: fd22 (PID feedback value, 0.01Hz)
7: fd06 (Input terminal status)
8: fd07 (Output terminal status)
9: fe35 (RR input, 0.01%)
10: fe36 (RX input, 0.01%)
11: fe37 (II input, 0.01%)
12: fd04 (Input voltage (DC detection), 0.01%, With
filter)
13: fd16 (Estimated speed (real-time value), 0.01Hz)
14: fd18 (Torque, 0.01%, With filter)
15:fe60 (My monitor)
16:fe61 (My monitor)
17:fe62 (My monitor)
18:fe63 (My monitor)
19: f880 (Free notes)
20: fd29 (Input power, 0.01kW, With filter)
21: fd30 (Output power, 0.01kW, With filter)
22: fe14 (Cumulative operation time, 1hour)
23: fe40 (FM terminal output monitor, 0.01%)
24: fe41 (AM terminal output monitor, 0.01%)
25: fd20 (Torque current, 0.01%, With filter)
26: fd23 (Motor overload factor, 0.01%)
27: fd24 (Drive overload factor, 0.01%)
28: fd25 (PBR overload factor, %)
29: fd26 (Motor load factor, %)
30: fd27 (Drive load factor, %)
31: fe56 (Pulse train input, pps)
32: fe70 (Drive rated current, 0.1A)
33: fe76 (Input Watt-hour, 0.1kWh  10
34: fe77 (Output Watt-hour, 0.1kWh  10
35: fd83 (IGBT temperature, degree C)
f519
.
f749
.
INV: Inverter
INV → PLC
PKW: Parameter ID/value
PKW1(PKE)
PKE: Parameter ID (1st and 2nd octet)
PKW2(IND)
IND: Sub-index (3rd octet),
PKW3(PWE1)
PKW4(PWE2)
PWE: Parameter value (5th until 8th octet)
c021
c022
- 25 -
E6581738④
f749
4th octet is reserved
) **
f749
) **