Commissioning, inspection, maintenance

Checking the combustion quality

Fig. 44
1. Connect a flue gas analyser at flue gas port
the boiler flue connection.
Note
The fuel cell module must be in operation (power
generation) for the measurement.
2. Check the CO content.
The CO content must be < 100 ppm for all gas
types.

Checking the flue system for unrestricted flow and leaks

Fitting the front panels (fuel cell module)

To fit the front panels: See page 37.

Instructing the system user

The system installer should hand the operating instruc-
tions to the system user and instruct the user in oper-
ating the system.