Daikin VRV REYQ96XATJU Installation Manual page 37

Hide thumbs Also See for VRV REYQ96XATJU:
Table of Contents

Advertisement

[2-35]=
Height difference setting
Default value=1.
In case the outdoor unit is installed in the lowest position
(indoor units are installed on a higher position than outdoor
units) and the height difference between the highest indoor
unit and the outdoor unit exceeds 130 ft. (40 m), the setting
[2-35] should be changed to 0.
Other changes/limitations to the circuit apply, for more
information see 7.5. System piping (length) limitations on
page 11.
[2-45]=
Low ambient cooling
Default value=0.
Value
[2-45]
0
1
This setting is not applicable to multi Branch Selector unit.
For more information about this setting, refer to the service
manual.
[2-47]=
T
target temperature during heat recovery operation
e
Default value=0.
Value
[2-47]
0
2
3
4
5
6
7
Change [2-47]=0, 2-7 in function of required operation
method during heat recovery operation.
For more information and advice about the effect of these
settings, see 15.3. Energy saving and optimum operation.
[2-49]=
Height difference setting
Default value=0.
In case the outdoor unit is installed in the highest position
(indoor units are installed on a lower position than outdoor
units) and the height difference between the lowest indoor
unit and the outdoor unit exceeds 164 ft. (50 m), the setting
[2-49] has to be changed to 1.
Other changes/limitations to the circuit apply, for more
information see 7.5. System piping (length) limitations on
page 11.
[2-62]=
Cooling and heating capacity learning control
Default value=0.
Value
[2-62]
0
1
2
3
Adjust cooling and heating system operation to achieve
stable capacity.
Note: This setting may result in a longer reaction time to
large load variations.
3P477778-7G
English
Description
No low ambient cooling available.
(default)
Low ambient cooling available.
T
target
e
Auto (default)
43°F (6°C)
45°F (7°C)
46°F (8°C)
48°F (9°C)
50°F (10°C)
52°F (11°C)
Description
OFF
Cooling adjustment
Heating adjustment
Cooling and heating adjustment
[2-81]=
Cooling comfort setting
Default value=1.
Value
[2-81]
0
1
2
3
Change [2-81]=0, 1, 2 or 3 in function of required limitation.
This setting is used in conjunction with setting [2-8] and
[2-47].
For more information and advice about the effect of these
settings, see 15.3. Energy saving and optimum operation.
[2-82]=
Heating comfort setting
Default value=1.
Value
[2-82]
0
1
2
3
Change [2-82]=0, 1, 2 or 3 in function of required limitation.
This setting is used in conjunction with setting [2-9].
For more information and advice about the effect of these
settings, see 15.3. Energy saving and optimum operation.
[2-92]=
Te target temperature upper limit
Default value=1.
Value
[2-92]
0
1
2
If Auto Te, then use this setting to address different load pro-
files. If the frequent operation is at lower system load, then
use a higher setting under [2-92].
Note: In high humid areas, it is recommended to keep this
setting to 0 or 1.
Cooling comfort setting
Eco
Mild (default)
Quick
Powerful
Heating comfort setting
Eco
Mild (default)
Quick
Powerful
Te target temperature upper limit
L
M
H
34