Daikin VRV REYQ96XATJU Installation Manual page 36

Hide thumbs Also See for VRV REYQ96XATJU:
Table of Contents

Advertisement

[2-26]=
Low noise operation start time
Change [2-26]=1, 2 or 3 in function of required timing.
Default value=2.
Value
[2-26]
1
2
3
This setting is used in conjunction with setting [2-22].
[2-27]=
Low noise operation stop time
Default value=3.
Value
[2-27]
1
2
3
This setting is used in conjunction with setting [2-22].
[2-30]=
Power consumption limitation level (step 1) via the external
control adaptor (DTA104A61/62)
If the system needs to run under power consumption limita-
tion conditions when an external signal is sent to the unit,
this setting defines the level power consumption limitation
that will be applied for step 1. The level is according to the
table.
Default value=3.
Change [2-30]=1, 2, 3, 4, 5, 6, 7 or 8 in function of required
limitation.
Value
[2-30]
1
2
3
4
5
6
7
8
[2-31]=
Power consumption limitation level (step 2) via the external
control adaptor (DTA104A61/62)
If the system needs to run under power consumption limita-
tion conditions when an external signal is sent to the unit,
this setting defines the level power consumption limitation
that will be applied for step 2. The level is according to the
table.
Default value=1.
Change [2-31]=1, 2 or 3 in function of required limitation.
Value
[2-31]
1
2
3
33
Start time automatic low noise
operation (approximately)
8:00 p.m.
10:00 p.m. (default)
12:00 a.m.
Start time automatic low noise
operation (approximately)
6:00 a.m.
7:00 a.m.
8:00 a.m. (default)
Power consumption limitation
(approximately)
60%
65%
70% (default)
75%
80%
85%
90%
95%
Power consumption limitation
(approximately)
40% (default)
50%
55%
[2-32]= Forced, all time, power consumption limitation operation
(no external control adaptor is required to perform power
consumption limitation)
If the system always needs to run under power consump-
tion limitation conditions, this setting activates and defines
the level power consumption limitation that will be applied
continuously. The level is according to the table.
Default value=0 (OFF).
Value
[2-32]
0
1
2
Change [2-32]=0, 1 or 2 in function of required limitation.
[2-34]=
Indoor unit fan tap setting
Indoor units fan speed limitation related to connection ca-
pacity and outdoor air temperature for energy saving.
Default value=0.
Value
Indoor unit fan tap setting
[2-34]
Fan speed is limited to L tap when indoor units
0
capacity ≥130%.
In heating mode, fan speed is limited to L tap
1
when indoor units capacity ≥130%.
Fan speed follows the setting of remote controllers
2
(not limited by indoor units connection capacity).
See the service manual for other indoor unit fan tap settings.
Restriction reference
Function not active (default)
Follows [2-30] setting
Follows [2-31] setting
3P477778-7G