Y branch, Header and HR unit connection pattern
Pattern 1
B
HR1
1
2
14.5kW
14.5kW
(48kBtu/h)
(48kBtu/h)
(48kBtu/h)
• Impossible installation : Head branch pipe → HR unit
Pattern 2
HR1
B
1
2
3
4
2.1kW
2.1kW
2.1kW
2.1kW
(7kBtu/h)
(7kBtu/h)
(7kBtu/h)
(7kBtu/h)
• Impossible installation : HR unit → Head branch
pipe → Y and Head branch pipe.
Pattern 3
1
2
14.5kW
14.5kW
(48kBtu/h)
(48kBtu/h)
• The maximum total capacity of indoor
units is 58kW(192 kBtu/h).
Pattern 4
HR1
B
1
2
3.63kW
3.63kW
(12kBtu/h)
(12kBtu/h)
• The maximum total capacity of a branch
pipe of HR unit is 14.5kW(48 kBtu/h).
HR2
3
4
14.5kW
14.5kW
(48kBtu/h)
A
5
6
7
2.1kW
7.25kW
7.25kW
(7kBtu/h)
(24kBtu/h)
(24kBtu/h)
HR1
3
4
14.5kW
14.5kW
(48kBtu/h)
(48kBtu/h)
3
4
3.63kW
3.63kW
(12kBtu/h)
(12kBtu/h)
Pattern 5
A
(48kBtu/h)
Pattern 6
HR1
B
1
2
7.25kW
7.25kW
(24kBtu/h)
(24kBtu/h)
Pattern 7
A
HR1
1
2
14.5kW
14.5kW
(48kBtu/h)
(48kBtu/h)
• * : Serial connection of HR units : Capacity sum of indoor units ≤ 192 kBtu/h
Pattern 8
A
HR1
1
2
14.5kW
14.5kW
(48kBtu/h)
(48kBtu/h)
• * : Maximum indoor units per a branch are 8 indoor units
Indoor Unit
Y Branch pipe
1
Low pressure Gas pipe
Outdoor
High pressure Gas pipe
Unit
Liquid pipe
• Pipe installation from outdoor units to HR units
: 3 pipes(Low pressure Gas pipe, High pressure Gas pipe, Liquid pipe)
• Pipe installation from HR units to indoor units
: 2 pipes(Gas pipe, Liquid pipe)
HR1
HR2
1
2
3
4
14.5kW
14.5kW
14.5kW
14.5kW
(48kBtu/h)
(48kBtu/h)
(48kBtu/h)
A
A
A
3
4
5
3.63kW
3.63kW
7.25kW
(12kBtu/h)
(12kBtu/h)
(24kBtu/h)
HR2
HR3
3
4
5
14.5kW
14.5kW
14.5kW
14.5kW
(48kBtu/h)
(48kBtu/h)
(48kBtu/h)
(48kBtu/h)
HR2
A
B
3
4
5
6
3.63kW
3.63kW
3.63kW
3.63kW
7.25kW
(12kBtu/h)
(12kBtu/h)
(12kBtu/h)
(12kBtu/h)
(24kBtu/h)
Head Branch pipe
B
A
Gas pipe
Indoor
HR1
Unit
Liquid pipe
*
6
*
7
8
7.25kW
(24kBtu/h)