ELECTRICAL WIRING
80
Central Control Connection at Indoor Unit side
Mode setting method
Master unit PCB DIP switch on : No.5
Compressor Input Current Limit
System Input Current Control
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using '
"Func" Push the '● ' button
Select the Function using '
"Fn20" Push the '● ' button
Select the Option using '
"oFF","op1"~"op10" Push the ' ● ' button
Compressor Input Current Limit mode is set
CAUTION
!
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• If use a function, capacity may go down.
Compressor Input Current Limit
', ' ' Button :
', ' ' Button :
', ' ' Button :
Mode
Compressor Input Current Limit
op1
op2
op3
op4
op5
op6
op7
op8
op9
op10
95 %
90 %
85 %
80 %
75 %
70 %
65 %
60 %
55 %
50 %