Download Print this page

LG MULTI V JRUV220LTE5 Installation Manual page 77

Advertisement

Compressor Max. Frequency Limit
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ' ', ' ' Button :
Select the Function using
"oFF","op1","op9" Push the '●' button
Function setting
• Ask an authorized technician to setting a function.
• If use a function, first install a Central controller.
"Func" Push the '●' button
"Fn 12" Push the '●' button
Cool & Heat Selection mode is set
Setting
oFF
op1
op2
op3
op4
op5
op6
op7
op8
op9
CAUTION
!
ELECTRICAL WIRING
Button :
Inverter (Hz)
-
143 Hz
135 Hz
128 Hz
120 Hz
113 Hz
105 Hz
98 Hz
90 Hz
83 Hz
77