9.3.3.9 High temperature protection of condenser (ODU P5)
When outdoor pipe temperature is more than 65°C, the unit will stop, and unit runs again when outdoor pipe
temperature less than 52°C.
High temperature protection of 
condenser
Check whether the
condenser temperature is
Higher than 65°C
Yes
Check whether the outdoor
ambient temperature is
higher than 50℃
No
Check if the outdoor unit 
ventilation is good
Yes
Check if the outdoor fan runs 
properly
Yes
Check whether the heat
exchanger is dirty
No
Replace outdoor main
board
No
Refrigerant is not enough add the 
refrigerant
No
Check whether the refrigerant
system is ok
 
No
Yes
Stop the unit
No
Make the outdoor unit ventilate well
please refer to the solution of fan 
speed has been out of control 
No
malfunction . Find out the cause and 
have it solved.
Yes
Clean the heat exchanger
Check the connection 
between temperature 
sensor and PCB.
Yes
Check whether the
resistance of condenser
temp. sensor is normal
refer to the Appendix 1
Yes
No
Correct the connection
No
Replace the temperature sensor