13. C
AUTION FOR REFRIGERANT LEAKS
(Points to note in connection with refrigerant leaks.)

13.1. Introduction

The installer and system specialist shall secure safety against
leakage according to local regulations or standards. The
following standards may be applicable if local regulations are
not available.
This unit, like other air conditioning systems, uses R-410A as
refrigerant. R-410A itself is an entirely safe non-toxic, non-
combustible refrigerant. Nevertheless care must be taken to ensure
that air conditioning facilities are installed in a room which is
sufficiently large. This assures that the maximum concentration level
of refrigerant gas is not exceeded, in the unlikely event of major leak
in the system and this in accordance to the local applicable
regulations and standards.

13.2. Maximum concentration level

The maximum charge of refrigerant and the calculation of the
maximum concentration of refrigerant is directly related to the
humanly occupied space in to which it could leak.
The unit of measurement of the concentration is kg/m
kg of the refrigerant gas in 1 m
Compliance to the local applicable regulations and standards for the
maximum allowable concentration level is required.
According to the appropriate European Standard, the maximum
allowed concentration level of refrigerant to a humanly space for
R-410A is limited to 0.44 kg/m
3
1
direction of the refrigerant flow
2
room where refrigerant leak has occurred (outflow of all the
refrigerant from the system)
3
BP unit
Pay special attention to places, such as a basements, etc. where
refrigerant can stay, since refrigerant is heavier than air.

13.3. Procedure for checking maximum concentration

Check the maximum concentration level in accordance with steps 1
to 4 below and take whatever action is necessary to comply.
1
Calculate the amount of refrigerant (kg) charged to each system
separately.
+
amount of refrigerant
in a single unit
system (amount of
refrigerant with
which the system is
charged before
leaving the factory)
NOTE
Where a single refrigerant facility is divided into
2 entirely independent refrigerant systems, use
the amount of refrigerant with which each
separate system is charged.
RMXS112~160D7V3B
Super Multi Plus System air conditioner
4PW19516-1B
3
(the weight in
3
volume of the occupied space).
3
.
1
2
=
additional charging
total amount of
amount (amount of
refrigerant (kg)
refrigerant added
in the system
locally in accordance
with the length or
diameter of the
refrigerant piping)
2
Calculate the smallest room volume (m
In a case such as the following, calculate the volume of (A), (B)
as a single room or as the smallest room.
A.
Where there are no smaller room divisions
1
BP unit
B.
Where there is a room division but there is an
opening between the rooms sufficiently large to
permit a free flow of air back and forth.
1
opening between rooms
2
partition
(Where there is an opening without a door or where there
are openings above and below the door which are each
equivalent in size to 0.15% or more of the floor area.)
3
BP unit
3
Calculating the refrigerant density using the results of the
calculations in steps 1 and 2 above.
total volume of
refrigerant in the
refrigerant system
3
size (m
) of smallest
room in which there is
an indoor unit installed
If the result of the above calculation exceeds the maximum
concentration level then make similar calculations for the second
then third smallest room and so until the result falls short of the
maximum concentration.
4
Dealing with the situations where the result exceeds the
maximum concentration level.
Where the installation of a facility results in a concentration in
excess of the maximum concentration level then it will be
necessary to revise the system.
Please consult your supplier.
14. D
ISPOSAL REQUIREMENTS
Dismantling of the unit, treatment of the refrigerant, oil and eventual
other parts, should be done in accordance with the relevant local and
national regulations.
3
)
1
3
1
2
maximum concentration level (kg/m
Installation manual
3
)
18