1 Service Information

1.1.

Operation range

1.1.1.
Power supply
The applicable voltage range for each unit is given in the following table. The working voltage among the three phases must be
balanced within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the
rated voltage.
MODEL
CU-
L50DBE5
L50DBE8
1.1.2.
Indoor and outdoor temperature
• Model 50Hz CU-L50DBE5, CU-L50DBE8
Operating
Cooling
Heating
Unit Main Power
Phase, Volts
1~240
3N~380
3N~400
3N~415
Hz
Indoor Temp. (D.B./W.B.) (“C)
Max
50
32/23
50
27/-
Hz
50
50
50
50
Min
21/15
16/-
3
Applicable Voltage
Max
Min
264
216
418
342
440
360
457
374
Outdoor Temp. (D.B./W.B.) (“C)
Max
Min
43/-
-15/-
24/18
-20/-